4-4-3 Troubleshooting for outdoor unit

If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
LED Display
No.
Red
Green
-
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Samsung Electronics
Displayed
PCB Assy
Yellow
Normal operation
(MAIN : Indoor Outdoor : Green ON)
MAIN/INVERTER
(INVERTER : MAIN PCB INVERTER PCB :
Green ON)
Unit quantity miss matching between
MAIN
indoor and outdoor.
Abnormal state, no communication
MAIN/INVERTER
between Indoor and Outdoor Main PCB
1min. Time out of communcation
MAIN/INVERTER
error(Main Inverter)
MAIN
Outdoor temp sensor error
MAIN
Cond. temp sensor error
MAIN
Discharge temp sensor error
MAIN
OLP Sensor Error
Detection of Outdoor Freezing when
MAIN
Comp. Stop
Protection of Outdoor Overload when
MAIN
Comp. Stop
Discharge temperature of a compressor
MAIN
in an outdoor unit is overheated.
Heating operation is not available since
the outdoor air temperature is over 30°C.
MAIN
Cooling operation is not available since
the outdoor air temperature is lower than
-5°C.
MAIN/INVERTER
Outdoor unit BLDC Fan 1 or Fan 2 error
MAIN/INVERTER
Comp. Starting error
MAIN
Primary Current Trip error
MAIN
Over current trip / PFC over current error
MAIN/INVERTER
IPM(IGBT Module) Over Current(O.C)
MAIN/INVERTER
Comp. Over load error
MAIN/INVERTER
DC-Link voltage under/over error
MAIN/INVERTER
Comp. wire missing error
MAIN/INVERTER
Current sensor error
MAIN
Outdoor EEPROM error
IPM(IGBT Module) or PFCM Temperature
MAIN/INVERTER
sensor Error
MAIN/INVERTER
PFC Overload Error
MAIN/INVERTER
IPM is over heated.
MAIN
GAS Leak error
Capacity miss match between indoor and
MAIN
outdoor
Option code miss matching among the
MAIN
indoors (only for DPM)
Meaning
Check indoor quantity
setting in outdoor (Refer
to page 17.)
Check electrical
connection and setting
Check electrical
connection and setting
Check Outdoor sensor
Open/Short
Check Cond. sensor
Open/Short
Check Discharge sensor
Open/Short
Check OLP sensor
Open/Short
Check Outdoor Cond.
Check Comp. when it start
Heating
Cooling
FAN1 error
FAN2 error
Check OLP sensor
Check AC Power or
DC_Link voltage
Check Comp. wire
Check Outdoor Inverter
PBA
Check Outdoor EEPROM
date
Check Outdoor Inverter
PBA
Check Outdoor Inverter
PBA
Check Outdoor Inverter
PBA
Check indoor and outdoor
unit model
Check indoor and outdoor
unit model
Check indoor option code
Remarks
Error Code
-
E201
E202
E203
E221
E231
E251
E320
E403
E404
E416
E440
E441
E458
E475
E461
E462
E463
E464
E465
E466
E467
E468
E471
E474
E484
E500
E554
E556
E557
Off
Blink
On