Mitsubishi Heavy Industries FDT71VNXVD Service Manual page 62

Hyper inverter packaged air-conditioners
Hide thumbs Also See for FDT71VNXVD:
Table of Contents

Advertisement

Error code
Remote controller:
E6
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger thermistor (ThI-R1,
R2 or R3).
3. Condition of Error displayed
• When the temperature
thermistor detects -50 (-28)°C
or lower for 5 (15) seconds
continuously, the compressor
stops. After 3-minutes delay,
the compressor starts again
automatically, but if this
error occurs again within
60 minutes after the initial
detection.
Note (1) Value in ( ) are for the
   models SRK 50, 60.
• Or if 70°C or higher is
detected for 5 seconds
continuously. (FDTC, FDT,
FDEN, FDUM, FDU series only)
4. Presumable cause
• Defective indoor heat
exchanger thermistor
connector
• Indoor heat exchanger
temperature thermistor
anomaly
• Faulty indoor control PCB
Note:
LED
Green
Red
Content
Indoor
Keeps flashing 1 time flash
Keeps flashing Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Is the
connection of indoor heat
exchanger temperature thermistor
connector OK?
YES
Are
characteristics of indoor
heat exchanger temperature
thermistor OK?
Temperature-resistance characteristic
(Broken wire)
15
10
5
(Shot circuit)
0
10
20
Temperature (°C)
-
-
72
72
Indoor heat exchanger
temperature thermistor anomaly
NO
NO
YES
°C
5k at 25
30
40
50
-
-
'10 • PAC-SM-137$
Countermeasure
Correct.
Insert connector
securely.
Defective indoor heat
exchanger temperature
thermistor
Replace.
Defective indoor control
PCB
Replace.
(Defective indoor unit heat
exchanger temperature
thermistor input circuit)