DIP switch setting list
Switches
Address No. setting at plural indoor units control by 1 R/C
SW2
SW5-1
Master/Slave setting
SW5-2
SW6-1
SW6-2
Model selection
SW6-3
SW6-4
SW7-1
Test run, Drain motor
SW7-2
Reserved
SW7-3
Powerful mode
Reserved
SW7-4
Superlink terminal spare
JSL1
Table 1: Indoor unit model selection with SW6-1-SW6-4
40V
SW6-1
1
SW6-2
1
SW6-3
0
SW6-4
0
Table 2: Indoor unit Master/Slave setting with SW5-1,SW5-2 (Not used in Oceania)
0: OFF
SW5-1 SW5-2
Master
0
Slave1
0
Slave2
1
Slave3
1
Description
Master * /Slave
Normal * /Test run
Valid*/Invalid(FDU only)
Normal * /switch to spare
* Default setting
50V
60V
71V
100V
1
1
1
1
0
1
0
1
1
1
0
0
0
0
1
1
1:ON
0
1
0
1
-
33
Default setting
0-F
0
OFF
See table 2
OFF
As per model
See table 1
OFF
Normal
OFF
keep OFF
ON
Valid
keep OFF
OFF
With
0: OFF
1:ON
125V
140V
0
1
0
0
1
1
1
1
-
'10 • PAC-SM-137A