Model FDC 125VNX, 140VNX
2)
Model
a)
Replace the PCB after elapsing 3 minutes from power OFF.
b)
Measurement was done on both ends of connector(CNA1) during measurement, the voltage(DC) might charged
the electrolytic capacitor, be sure that the voltage is discharged sufficiently. (Refer to Fig.1)
c)
Disconnect the connectors from the control PCB.
d)
Disconnect the white or blue wiring passing through CT1 on the PCB before replacing the PCB.
e)
Match the setting switches (SW3-5, JSW, SW(J5-7)) with the former PCB.
f)
Tighten up a screw after passing white or blue wiring through CT1 of the changed.
g) Please connect the connectors with the same place. (Confirm the connectors are not half inserted.)