Mitsubishi Heavy Industries FDT71VNXVD Service Manual page 16

Hyper inverter packaged air-conditioners
Hide thumbs Also See for FDT71VNXVD:
Table of Contents

Advertisement

(3)
Compressor soft start control
(a) Compressor protection start I
[Control condition] Normally, the compressor operation frequency is raised in this start pattern.
[Control contents] 1) Starts with the compressor's target frequency at A rps.
(b) Compressor protection start III
[Control condition] Number of compressor starts is only 1 counted after the power supply breaker ON.
[Control contents]
1)
Low frequency operation control during cooling/dehumidifying
[Control condition] Upon establishing the conditions of compressor protection start III, the low frequency
[Control contents]
2)
Low frequency operation control during heating
[Control condition] When the conditions of compressor protection start III are established and one of following conditions
[Control contents]
However, when the ambient air temperature (Tho-A) is 35°C or higher during cooling/
dehumidifying or the indoor return air temperature (Th
starts at C rps.
2) At 30 seconds after the start of compressor, its target frequency changes to B rps and the
compressor is operated for 2 - 4 minutes with its operation frequency fixed at B rps.
Model
Operation mode
Cooling/Dehumidifying
71
Heating
Cooling/Dehumidifying
100
Heating
Cooling/Dehumidifying
125, 140
Heating
Operates by selecting one of following start patterns according to the operation mode and the
outdoor air temperature (Tho-A).
operation control is performed during cooling/dehumidifying.
a) Starts with the compressor's target frequency at A rps. When the outdoor air temperature
(Tho-A) is 35°C or higher, it starts at C rps.
b) At 30 seconds after the compressor start, the compressor's target frequency is changed to B
rps and the compressor's operation frequency is fixed for 10 minutes.
Model
Operation mode
71
Cooling/Dehumidifying
100
Cooling/Dehumidifying
125, 140
Cooling/Dehumidifying
a) and b) is satisfied, the low number of revolutions operation control is performed during heating.
a) At 30 minutes or more after turning the power supply breaker on
b) Compressor underneath temperature (Tho-H) is 4°C or higher and the difference from the
outdoor air temperature (Tho-A) becomes 4°C or higher. [model 200, 250 only]
a) Starts the compressor with its target frequency at A rps. However, when the indoor unit
return air temperature (Th
b) At 30 seconds after the start of compressor, the compressor's target frequency is changed to
B rps and the compressor's operation frequency is fixed for 10 minutes.
Model
Operation mode
71
100
125, 140
-
-A) is 25°C or higher during heating, it
I
A rps
42
62
55
55
45
45
A
rps
42
55
45
-A) is 25°C or higher, it start at C rps.
I
A
rps
42
Heating
55
Heating
45
Heating
-
21
'10 • PAC-SM-137A
B rps
C rps
42
40
62
40
55
30
55
30
45
25
45
25
B
C
rps
rps
42
40
55
30
45
25
B
C
rps
rps
42
40
55
30
45
25