(2) Installation of remote controller
(Option parts)
(a) Selection of installation location
Avoid the following locations
1) Direct sunlight.
2) Close to heating device.
3) Highly humid or water splashing area.
4) Uneven surface.
(b) Installation procedure
a) Exposed fiting
1) Open the remote controller case.
• Put a screw driver (flat-head) into the concavity
made on the upper part of a remote controller and
twist it lightly to open the casing.
2) The cord of a remote controller can only be pulled
out in the upward direction.
• Cut off with nippers or a knife a thin walled part
made on the upper end of the rmote controller
bottom casing, and then remove burrs with a file
or the like.
3) Fix the remote controller bottom casing onto a wall
with two wood screws supplied as accessories.
4) Connect the remote controller cord to the termi-
nal block. Connect between the remote controller
terminals (x, Y) and the indoor unit terminals
(x, Y). (x and Y have no polarity.)
Wiring path will be as shown below depending on
the direction to take out.
Top
PCB
Y
Bottom
Wire
Take-out at top right
• Cord used in the remote controller should be 0.3
2
mm
- max. 0.5 mm
section laid within the remote controller casing.
The length of each wire that should be left after a
sheath is removed is as follows.
Take-out at top right
Take-out at center
X wire: 215mm
Y wire: 195mm
5) Replace the top casing as before.
6) Use a cord clamp to attach the remote controller
cord to the wall.
Thin walled part
Upper
Lower case
Lower
Upper
Lower case
Lower
Sheath
Sheath
Top
Upper case
PCB
Y
Bottom
Wire
Take-out at center
2
. Remove a sheath for the
X wire: 170mm
ength of the
Y wire: 190mm
section where a
sheath is removed
(c) Recessed fitting
1) The Electrical box and remote controller (shield
2) Remove the upper case to the remote controller.
3) Attach the lower case to the Electricl box with two
4) Connect the remote controller cord to the remote
5) Installation work is completed by replacing the
6) Set the functions according to the types of indoor
Upper case

Precation in extending the remote controller cord

Maximum total extension 600m.
The cord should be a shielded wire.
For all types : 0.3mm
Note 1) Use cables up to 0.5mm
inside the remote controller casing and connect to a
different size cable at a vicinity point outside the remote
controller, if necessary.
Within 100-200m ÉÉÉÉ
The shielded wire should be grounded at one side only.
237
-
-
wire must be use in case of extension) are first
embedded.
emote
controller cord
Upper
Lower case
Lower
Cable outlet
Upper
Cut off with a knife or the like thin walled parts
intended for screw holes, and then fix it with
screws.
Lower
Cable outlet
M4 screws. (Head diameter must be 8 mm).
Choose either of the following two positions in
fixing it with screws.
controller.
Refer to [Exposed Fitting].
top casing onto the bottom casing as before.
unit. See section "Setting function". Refer to page
310.
wo M4 screws
(Head diameter must be 8mm)
(not included)
2
2 cores
2
0.5
mm
Within 300m ÉÉÉÉ
0.75 mm
Within 400m ÉÉÉÉ
1.25 mm
Within 600m ÉÉÉÉ
2.0
mm
Earth wiring
Indoor unit
This side is not grounded)
Electrical box
Not included
maximum) for those laid
2
2 cores
2
2 cores
2
2 cores
2
2 cores
Remote controller cord
Shielded wire)
Remote controller