minutes, thedraft r egulator should besetto between -0.025"
and -0.060" W.C.
3.3.5
Overfire pressure test
The overfire draft that is taken through the observation
port,
located above the burner, is a measurement
necessary
to
determine
if there is a blockage in the heat exchanger or the
flue pipe. Refer to the Technical Specifications
in this manual
for overfire pressure values. A high pressure condition may be
caused by excessive combustion air, due to the air band being
too wide open, or a lack of flue draft (chimney effect) or some
other blockage, such as soot in the secondary section of the
heat exchanger
or the use of an oversize nozzle input or high
pressure pump.
3.3.6
Vent Temperature
Test
1.
After having
adjusted
the burner
combustion,
insert
a
thermometer
into the test hole in the breech pipe;
2.
The total vent temperature
should be between 204 and
302°C (400 and 575°F).
If not, check for improper
air
temperature
rise, pump pressure, nozzle size or a badly
sooted heat exchanger.
CAUTION
Low flue
gas
temperature
increases
the
risk
of
condensation. Adjust the total temperature
at or higher
then 204°C (400°F) in order for the heat exchanger
warranty to remain in force.
2.
Press the reset button on the burner primary control
(relay);
3.
Set the thermostat higher than room temperature;
4.
If the burner motor does not start or ignition fails, turn
off the disconnect
switch and CALL A QUALIFIED
SERVICE TECHNICIAN.
CAUTION
Do not attempt to start the burner when excess oil has
accumulated,
when the furnace is full of vapour or when
the combustion chamber is hot.
3.3.7
Supply
Air Temperature
Rise Test
1.
Operate the burner for at least 10 minutes;
2.
Measure the air temperature in the return air plenum;
3.
Measure
the air temperature
in the supply
duct just
outside the range of radiant heat from the heat exchanger.
0.3 m (12") from the plenum of the main take-off is usually
sufficient;
4.
The temperature
rise is calculated
by subtracting
the
return air temperature from the supply air temperature;
5.
If
the
temperature
rise
is
lower
or
exceeds
the
temperature specified in Table 6, change to the next lower
or higher blower speed tap, until the temperature rise falls
to the target. If the excessive temperature
rise cannot be
increased or reduced by changing fan speed, investigate
for ductwork
obstructions,
dirty
or improper
air filter,
improper
firing
caused by improper
pump pressure
or
nozzle sizing.
3.3.8 Limit Control Check
After operating the furnace for at least 15 minutes, restrict the
return air supply by blocking the filters or the return air register
and allow the furnace to shut off on High Limit. The burner will
shut off but the blower wilt continue to run.
Remove the obstruction
and the burner should restart after a
few minutes. The time required for the restart also depends on
the adjustment of the blower "OFF" delay.
3.3.9 Restart after Burner Failure
1.
Set the thermostat lower than room temperature;