Ducane CMP A Series Installation Instructions Manual page 7

Table of Contents

Advertisement

FAect
rical:
The control system depends on the correct polarity of the
power supply. Connect "hot" wire (H) and "ground" wire "G'"' as
shown in Figures 1.21 & 1.22. Reference table 1.20 for furnace
over current protection, current rating and wire size. Use copper
wire only for ll5V-supply
service to unit. When replacing any
original internal wiring, use only 105°C, 16 AWG copper wire.
Instructions
for wiring the thermostat are packed in the
thermostat (field supplied) box. Make the thermostat connections
as shown in Figures 1.21 & 1.22 at the 24-volt terminal board
located in the control box.
When installing optional accessories to this appliance, follow
the manufacturer's
installation
instructions
included with the
accessory.
Other than wiring for the thermostat, a minimum of
type T (63°F rise) must be used.
Figure 1.7
AIR INLET CONNECTOR
ASSEMBLY
CONNE_OR
GASKET
WARNING
The unit cabinet
must have an uninterrupted
or
unbroken
electrical
ground
to minimize
personal
injury if an electrical fault should occur. This may
consist of electrical wire or approved conduit when
installed
in accordance
with
existing
electrical
codes.
Do not use gas piping
as an electrical
ground.
Failure
to follow this warning can result
m an electrical
shock, fire, bodily harm. or loss of
life.
Installation
of Air Inlet Connector:
The air inlet connector must be installed on the top panel of
the furnace (See Figure 1.7). The connector, gasket, and mounting
screws are shipped in a bag located in the vestibule of the furnace.
The gasket is placed over the hole pattern in the top panel and the
connector is then secured to the top panel using the No. 10 X 5/8
sheet metal screws. The screws should be tightened securely, so
that the gasket seals the connector to the top panel in order to
prevent air leakage into the burner box. When installing furnace as
non-direct vent (one pipe), a field supplied PVC elbow (see Table
1.8 for size required) must be attached to the air inlet connector
with the elbow open end facing front (Figure 1.7). When installing
furnace as direct vent (two pipe), air inlet piping must match vent
pipe in length and configuration.
CAUTION
Terminate
the combustion
air intake in the same
pressure
zone
as the vent
outlet and as far as
possible
from
the air conditioning
unit or heat
pump, swimming
pools, swimming
pool pumping
units and dryer vents.
Venting & Termination Instructions:
Venting for this category IV furnace must be with schedule 40
PVC, CPVC or ABS pipe including all elbows and vent terminals.
All pipe and fittings must conform to the American Society for
Testing and Material (ASTM), and American National Standards
Institute (ANSI) Standards.
PVC primer and solvent cement used
to secure all PVC joints must conform to ASTM D2564. Common
venting with other condensing appliances
or non-condensing
appliance* is not allowed.
All combustion air and exhaust piping must be installed in
accordance with local codes and these instructions. For additional
venting
information
refer
to
ANSI/NFPA
211
Chimney,
Fireplaces, Vents and Solid Fuel Bumin_ Anoliances or Canadian
equivalenL
Refer to Tables 2.7 and 1.8 for the proper pipe diameters and
the minimum and maximum allowable vent lengths.
Table 2.7 DIRECT VENT (TWO PIPE) ALLOWABLE
VENT LENGTHS
MODEL
PIPEDIAM.
50
2_.
75U2
2 1_.
75U3A
75W
2_.
1_
3_.
125
3_.
MIN. VENT
MAX. VENT
5FT.
*:;OFT.
5FT.
* 50 FT.
5FT.
* 50 FT.
5zr.
* 50 F'r.
5FT.
*50FT.
* - Up to (5) 90 degree elbows may be used. Sweep elbows are poeretable but not
required.
2 - 45 degree elbows - 1-90 degree elbow.
20246506
Issue 9939
Page 7 of 22

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Ducane CMP A Series

Table of Contents