Blower Specifications - Ducane CMP A Series Installation Instructions Manual

Table of Contents

Advertisement

FURNACE
BLOWER
SPECIFICATIONS
AND AIR FLOW
DATA
(CFM)
Table
1.17
BLOWER
SYSTEM
BLOWER
EXTERNAL
STATIC
SPEED
(INWC)
0.1
I
0.2
I
0.3
I
0.4
I
0.5
I
0.6
I
0.7
[
0.8
t
0.9
I
1.0
CMPA050U2
(10 X 6 WHEEL)
LOW
720
680
650
590
540
480
440
360
270
170
( 1/4 HP MOTOR)
IVIED
920
880
830
780
720
650
580
460
380
304)
Mtr PIN 20278901
HIGH
1100
1060
1010
960
900
790
680
570
470
350
CMPA050U3
(10 X 6 WHEEL)
LOW
1080
1060
1030
1000
965
905
840
765
655
525
(1/3 lip MOTOR)
IVIED
1330
1280
1225
1175
1110
1040
965
875
770
630
Mtr PtN 20054901
HIGH
14_)
1420
1360
1285
1205
1125
1070
985
880
750
CMPA075U2
(10 X 6 WHEEL)
LOW
780
770
760
750
730
700
685
620
520
390
(1/4 lIP MOTOR)
IVIED
950
940
930
920
900
825
775
695
605
480
Mtr P/N 20279001
HIGH
1255
1225
1195
1155
1110
1040
960
865
760
620
CM]PA07SU3
(10 X 6 WHEEL)
LOW
1080
1060
1030
10G0
965
905
840
765
655
525
(1/3 FIP MOTOR)
MED
1330
1280
1225
1175
1110
1040
965
875
770
630
Mtr PIN 20054901
HIGH
1490
1420
1360
1285
1205
I 125
1070
985
880
750
CMPA100U3
(10 X 9 WHEEL)
LOW
1270
1235
1190
1140
1080
1050
950
850
675
395
(1/3 HP MOTOR)
IVIED
1510
1465
1410
1350
1260
1210
1115
990
810
550
Mtr PIN 20279901
HIGH
1685
1655
1615
1540
1450
1330
1235
1130
960
720
CM]PA100U4
(12 X 9 WHEEL)
LOW
1420
1400
1360
1335
1290
1245
1190
1120
1060
995
(1/2 HP MOTOR)
IVIED
1715
1690
1665
1610
1550
1480
1400
1320
1245
1145
Mtr PIN 20062501
HIGH
2055
2020
1945
1865
1795
1710
1640
1535
1410
1340
CMPAI25U5
(12 X 12 WHEEL)
LOW
1425
1400
1375
1345
1320
1290
1245
1185
1120
1035
(3/4 HP MOTOR)
IVIED
1980
1940
1895
1835
1785
1720
1645
1575
!475
1385
Mtr PIN 20055001
HIGH
2395
2340
2275
2210
2115
2025
1925
1825
1720
1610
NOTES:
1.
Airflow
values
in cubic
feet per minute
(CFM)
rounded
to nearest
five (5) CFM.
2.
Data
taken
without
filters
in
place.
WARNING
When operating
the furnace in the heating mode, the Static pressure
and the temperature
rise (supply air
temperature
minus return air temperature)
must be within those limits specified on the rating label.
Failure
to
follow
this warning
could
lead to severe
furnace
damage.
WARNING
Turn OFF all gas and electrical power to furnace before performing
any maintenance
or service on unit
(unless specific
test requires
gas and electrical
supplies).
Failure
to take this precaution
may result in
personal injury due to electrical shock or uncontrolled gas leakage.
20246506
Issue 9939
Page 17 of 22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents