Desa LDL3930NRB Owner's Operating & Installation Manual page 9

Table of Contents

Advertisement

INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from floor, ceiling, and adjoin-
ing wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42", Front 36"
LOG SIZING REQUIREMENTS
Minimum Firebox
Height Depth
17"
14"
* Measured at 14" depth.
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fireplace, or listed
vent-free firebox.
Minimum Clearances For Side
Combustible Material, Side Wall, and
Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
/
" from the wall. This com-
1
2
bustible material must be 4" from the side
of the fireplace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer's instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fireplace
opening to the ceiling should not be less
than 42".
121486-01F
INSTALLATION
Continued
Front
Rear *
Width
Width
34"
24"
www.desatech.com
Example
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 11.
MINIMUM NONCOMBUSTIBLE
MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow the infor-
mation on this page.
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the fireplace
hood accessory. See Figure 5, page 10 for
minimum clearances.
*
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ldl3930prb

Table of Contents