Compressor Control - Fujitsu AS* A09LEC Service Instruction

Split type room air conditioner wall mounted type
Table of Contents

Advertisement

8. COMPRESSOR CONTROL

1. OPERATION SPEED RANGE
The operation speed of the compressor is different based on the operation mode as
shown in the table 10.
(Table 10 : Compressor operation speed range)
ASYA09LEC
ASYA12LEC
2. OPERATION SPEED CONTROL AT START UP
The compressor speed soon after the start-up is controlled as shown in the figure 11.
(Fig.11 : Compressor control at start-up)
119rps
108rps
97rps
87rps
74rps
56rps
80sec
Cooling
Minimum
Maximum
18rps
64rps
18rps
96rps
60sec
60sec
Heating
Minimum
Maximum
18rps
119rps
18rps
119rps
180sec
60sec
01-09
Dry
Minimum
Maximum
23rps
30rps
25rps
33rps
Time
60sec