2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
● areas where leakage of flammable gas may be expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the performance of the unit.
● locations where external air may enter the room directly. This may cause "condensation" on the air discharge ports, causing them to
spray or drip water.
● locations where the remote controller will be splashed with water or affected by dampness or humidity.
● installing the remote controller behind curtains or furniture.
● locations where high-frequency emissions are generated.
DO:
● select an appropriate position from which every corner of the room can be uniformly cooled.
● select a location where the ceiling is strong enough to support the weight of the unit.
WARNING
The installation position must be able to support a load four times the indoor unit weight.
● select a location where tubing and drain pipe have the shortest run to the outdoor unit.
● allow room for operation and maintenance as well as unrestricted air flow around the unit.
● install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length (L) from the
outdoor unit as detailed in the installation manual packed with the outdoor unit.
● allow room for mounting the remote controller about 3.3ft. (1m) off the floor, in an area that is not in direct sunlight or in the flow of cool
air from the indoor unit.
NOT E
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 9.8ft. (3 m).
3.3ft. (1000mm)
or more
Obstacles
* If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.
1.64ft. (500mm)
or more
Floor
1.64ft. (500mm)
1.64ft. (500mm)
or more
6
or more
Fig. 2-1