A.O. Smith ADMR - 40 Installation, User And Service Manual page 69

Commercial atmospheric water heater
Hide thumbs Also See for ADMR - 40:
Table of Contents

Advertisement

Symptom
Cause
S04 (blocking error)
Flue gas sensor is not
(correctly) connected.
Open circuit from flue
Defective flue gas
gas sensor 1.
sensor
Damaged wiring
S05 (blocking error)
Flue gas sensor is not
(correctly) connected.
Open circuit from flue
Defective flue gas
gas sensor 2.
sensor
Damaged wiring
S11 (blocking error)
Short circuit in sensor
circuit
Short circuit in the
temp. sensor T2 at the
bottom of the tank
S12 (blocking error)
Short circuit in sensor
circuit
Short circuit in sensor 1
of temperature sensor
T
at the top of the
1
(1)
tank
S13 (blocking error)
Short circuit in sensor
circuit
Short circuit in sensor 2
of temperature sensor
T1 at the top of the
(1)
tank
Instruction manual ADMR
Solution
(2)
Connect the flue gas sensor lead
to JP4.
Replace the flue gas sensor T
1
1. Measure the wire resistance of the sensor lead. This must be
± 0 Ohm.
2. Replace any damaged leads
(2)
Connect the flue gas sensor lead
to JP4.
Replace the flue gas sensor T
2
1. Measure the wire resistance of the sensor lead. This must be
± 0 Ohm.
2. Replace any damaged leads
Replace sensor T
and lead
2
Replace sensor T
and lead
1
Replace sensor T
and lead
1
Remark
See the ADMR electrical diagram (17 "Appendices")
To replace the necessary parts, you must contact your installation
engineer
To replace the necessary parts, you must contact your installation
engineer
See the ADMR electrical diagram (17 "Appendices")
To replace the necessary parts, you must contact your installation
engineer
To replace the necessary parts, you must contact your installation
engineer
To replace the necessary parts, you must contact your installation
engineer
To replace the necessary parts, you must contact your installation
engineer
To replace the necessary parts, you must contact your installation
engineer