(A) Application parameters
5.11.9

Multi-pump function (Advanced PID function)

PID control function can adjust the volume of water, etc. by controlling pumps. When the motor output is insufficient,
auxiliary motors can be driven by the commercial power supply. Up to three auxiliary motors can be connected.
Pr.
Name
578
Auxiliary motor
A400
operation selection
579
Motor connection
A401
function selection
580
MC switching interlock
A402
time
581
Start waiting time
A403
Auxiliary motor
582
connection-time
A404
deceleration time
Auxiliary motor
583
disconnection-time
A405
acceleration time
584
Auxiliary motor 1 starting
A406
frequency
585
Auxiliary motor 2 starting
A407
frequency
586
Auxiliary motor 3 starting
A408
frequency
587
Auxiliary motor 1
A409
stopping frequency
588
Auxiliary motor 2
A410
stopping frequency
589
Auxiliary motor 3
A411
stopping frequency
590
Auxiliary motor start
A412
detection time
591
Auxiliary motor stop
A413
detection time
POINT
POINT
• Refer to
page 378
• When using the SLEEP function, refer to
406
PARAMETERS
Initial value
FM
CA
0
0
1 to 3
0
1
0
2
3
1 s
0 to 100 s
1 s
0 to 100 s
0 to 3600 s
1 s
9999
0 to 3600 s
1 s
9999
60 Hz
50 Hz
0 to 590 Hz
60 Hz
50 Hz
0 to 590 Hz
60 Hz
50 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
5 s
0 to 3600 s
5 s
0 to 3600 s
to set PID control.
page 388
Setting
range
No auxiliary motor operation
Set the number of auxiliary motors to be run.
Basic system
Alternative system
Direct system
Alternative direct system
Set the MC switchover interlock time.
Set the time from when the MC is switched until it starts. Set
this time a little longer than the MC switching time.
Used to decrease the output frequency of the inverter when a
motor connection occurs. Set the deceleration time for
decreasing the output frequency.
The output frequency is not decreased when a motor
connection occurs.
Used to increase the output frequency of the inverter when a
motor connection occurs. Set the acceleration time for
increasing the output frequency.
The output frequency is not increased when a motor
connection occurs.
Set the frequency to start the auxiliary motor.
Set the frequency to stop the auxiliary motor.
Set the delay time until the auxiliary motor is started.
Set the delay time until the auxiliary motor is stopped.
to set the function.