Monitor Display Selection For Terminals Fm/Ca And Am - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

5.8.3
Monitor display selection for terminals FM/CA
and AM
The monitored statuses can be output as the following items: analog voltage (terminal AM), pulse train (terminal FM) for
the FM-type inverter, analog current (terminal CA) for the CA-type inverter.
The signal (monitored item) to be output to terminal FM/CA and terminal AM can be selected.
Pr.
Name
54
FM/CA terminal function
M300
selection
158
AM terminal function
M301
selection
55
Frequency monitoring
M040
reference
56
Current monitoring reference
M041
866
Torque monitoring reference
M042
290
Monitor negative output
M044
selection
291
Pulse train I/O selection
D100

FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.

FR-F820-03160(75K) or more, FR-F840-01800(75K) or more.

Function assigned to Pr.185 JOG terminal function selection.

Valid only for the FM type inverters.
(M) Monitor display and monitor output signal
Initial value
Setting range
FM
CA
1 to 3, 5 to 14, 17, 18,
21, 24, 34, 50, 52, 53,
61, 62, 67, 70, 85,
87 to 90, 92, 93, 95,
1
98
(output
frequency)
1 to 3, 5 to 14, 17, 18,
21, 24, 34, 50,
52 to 54, 61, 62, 67,
70, 86 to 96, 98
60 Hz
50 Hz
0 to 590 Hz
0 to 500 A

Inverter
Rated current
0 to 3600 A

150%
0 to 400%
0
0 to 7
0
1
10

11

0
20

21

100

Description
Select the monitored item to be output to
the terminal FM and terminal CA.
Select the monitored item to be output to
the terminal AM.
Set the full-scale value when outputting
the frequency monitor value to terminals
FM, CA and AM.
Set the full-scale value when outputting
the output current monitor value to
terminals FM, CA and AM.
Set the full-scale value when outputting
the torque monitor value to terminals FM,
CA and AM.
Set the availability of output with a minus
sign for the terminal AM, the operation
panel display, or monitoring via
communication. (Refer to
page
272)
Pulse train
Pulse train
input
output
(terminal JOG)
(terminal FM)
JOG signal
FM output


Pulse train input
FM output

High-speed pulse
JOG signal
train output

(50% duty)
High-speed pulse
Pulse train input
train output
(50% duty)
High-speed pulse
JOG signal
train output

(ON width fixed)
High-speed pulse
Pulse train input
train output
(ON width fixed)
High-speed pulse
train output
(ON width fixed)
Pulse train input
Output the pulse
train input without
changes.
PARAMETERS
5
GROUP
M
273

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents