For a full description of standard and extended parameters, please refer to the
Parameter List.
NOTICE
1. The inverter does not have a main power switch and is live when the mains
supply is connected. It waits, with the output disabled, until the RUN button is
pressed or for the presence of a digital ON signal at terminal 5 (rotate right).
2. If a BOP or an AOP is fitted and the output frequency is selected to be
displayed (P0005 = 21) the corresponding setpoint is displayed approximately
every 1.0 seconds while the inverter is stopped.
3. The inverter is programmed at the factory for standard applications on
Siemens four-pole standard motors that have the same power rating as the
inverters. When using other motors it is necessary to enter the specifications
from the motor's rating plate. See Figure 3-7 for details on how to read motor
data.
4. Changing motor parameters is not possible unless P0010 = 1.
5. You must set P0010 back to 0 in order to initiate a run.
Basic operation with the BOP/AOP
Prerequisites
P0010 = 0 (in order to initiate the run command correctly).
P0700 = 1 (enables the start/stop button on the BOP).
P1000 = 1 (this enables the motor potentiometer setpoints).
Press the green Button
Press the Button
When the inverter reaches 50 Hz, press the Button
decreased.
Change the direction of rotation with the Button
The red button stops the motor
44
to start the motor.
while the motor is turning. Motor speed increases to 50 Hz.
.
. Motor speed and display is
.
MICROMASTER 420
Operating Instructions
6SE6400-5AA00-0BP0
Issue 04/02