Flex Vent Installation - Monessen Hearth WDV Wideview WDV500 Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

Flex Vent InstallatIOn

1. Flexible UL1777 listed venting may be used in any venting application where rigid direct vent components
can be used. all restrictions, clearances and allowances that pertain to the rigid piping apply to
the flexible venting. Flex kits may not be modified. Flex kits may be
added to the end of a vent run made of rigid vent sections using pipe
manufacturer's approved flex to pipe adapters. This may occur
only if doing so does not violate any of the venting length, height,
routing, horizontal to vertical ratio requirements or clearance
considerations detailed in this manual.
2. The flex adapter starter kit (DVF8A/8) is used to attach flex
venting to the appliance starting collar. It includes 5" inner
and 8" outer adapter rings. Figure 24
The inner and outer adapter rings are required to start
all flex runs.
Never install damaged or torn flexible venting.
Over tightening clamps may rip, tear, or otherwise
damage flexible venting.
The adapter kit does not include individual pipe sec-
tions which may be purchased separately. (UL1777
listed type venting only.)
3. Start the flexible vent as follows:
A. Installing the inner flex adapter and pipe. Figure 24
1. Insert the long side of the 5" inner ring into
exhaust pipe, gently tap to seat into place, and secure with
screws.
2. Slide the small gear clamp over the inner flexible vent pipe,
and push out of the way.
3. Pull and extend the inner flexible vent.
4. Slide the inner vent onto the adapter collar, for a minimum
1
" overlap.
C\v
5. Locate the clamp at approximately 3/4" from the flex end and tighten.
6. Secure the clamped inner section with three self-tapping screws, drilled
equidistant, just above the clamp perimeter.
B. Installing the outer flex pipe. Figure 24
1. Firmly insert the 8" outer adapter ring into the outer appliance starting collar
and secure with screws.
2. Slide the large gear clamp over the outer flexible vent pipe, and push out
of the way.
3. Pull and extend the outer flexible vent.
4. Slide the outer vent onto the appliance collar outer adapter for a minimum
1
" overlap.
C\v
5. Locate the clamp at approximately 3/4" from the flex end and tighten.
6. Secure the clamped outer section with three self-tapping screws, drilled
equidistant, just above the clamp perimeter.
C. Routing UL1777 flex pipe.
1. Always maintain the required clearance when routing the flex vent assembly.
F l e x v e n t p i p e s p a c e r s : r e f e r t o
manufacturer's specifications for correct
positioning of the spacer springs to
maintain proper distance between inside
and outside pipe.
78D0011
1C\v" Flex-
ible Pipe
and Adapter
Outer
DVF8A
Inner Adapter
Outer Adapter
Figure 24 -
Typical Appliance Connection
UL1777
FP1972
Flex Vent
appliance connection
WDV Series Gas Fireplace
UL1777
Flex Vent
equidistant just
Appliance
Starting Collar
5° Radius
FP1973
Figure 25 -
Minimum Radius for Flex
FP1973
Vent Section
flex pipe bend
Screws
(3 places,
above gear
clamp)
19