VENT INSTALLATION

This fireplace must be vented to the outside. The venting system must NEVER be
attached to a chimney serving a separate solid fuel burning appliance. Each gas
appliance must use a separate vent system. Do not use common vent systems.
WARNING
Horizontal sections of this vent
system require a minimum of 3"
clearances to combustibles at the
top of the flue and 1" clearance
at the sides and bottom until the
flue penetrates the outside wall. A
minimum 1" clearance all around
the flue is acceptable at this point
of penetration.
Vertical sections of this vent
system require a minimum of 1"
clearance to combustibles on all
sides of the pipe.
16
Figure 12 - Combustible Clearances for Vent Pipe
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
� �
� �
� �
� �
A Minimum 1"
Clearance to
Combustibles
Permitted All Around
Flue at Outside Wall
42D0200