Fireplace Installation; Check Gas Type; Install Gas Piping - Monessen Hearth KHLDV400 Install And Operation Instructions

Khldv series direct vent gas fireplace
Table of Contents

Advertisement

FIrepLace InStaLLatIOn

cHecK GaS type

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install
fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or con-
version kit.
InStaLLInG GaS pIpInG tO FIrepLace / Burner SySteM LOcatIOn
a qualified installer or service person
must connect appliance to gas supply.
Follow all local codes.
InStaLLatIOn IteMS neeDeD
Before installing fireplace and burner system, make sure you have the items listed below.
External regulator (supplied by installer)
Sealant (resistant to propane/LP gas)
Sediment trap (recommended)
Tee joint
Approved flexible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge
connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do
not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with
the vent pointing down as shown in Figure 24. Pointing the vent down protects it from freezing rain or sleet.
External
Regulator
Figure 24 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
FP1977
external regulator
73D0024
Piping (check local codes)
Test gauge connection*
Pipe wrench
Equipment shutoff valve*
100 gallon (min)
Propane/LP
Supply Tank
Vent Pointing
Down
When using copper of flex connectors use only fittings
approved for gas connections. The gas control inlet is
3/8" NPT.
FP1977
For propane/Lp units, never connect
fireplace directly to the propane/Lp supply.
this burner system requires an external
regulator (not supplied). Install the external
regulator between the burner system and
propane/Lp supply.
use only new black iron or steel pipe. Internally
tinned copper or copper tubing can be used
per national Fuel code, section 2.6.3, providing
gas meets hydrogen sulfide limits, and where
permitted by local codes. Gas piping system
must be sized to provide minimum inlet
pressure (listed on data plate) at the maximum
flow rate (Btu/hr). undue pressure loss will
occur if the pipe is too small.
KHLDV Series Gas Fireplace