Sidewalls/Surrounds; Mantel And Wall Projections - Heatilator BIR42-B Installation Manual

Woodburning fireplace
Hide thumbs Also See for BIR42-B:
Table of Contents

Advertisement

D. Sidewalls/Surrounds
Locate adjacent combustible sidewalls a minimum of 24
in. (610 mm) from fireplace opening.
Mantle leg, surround, stub wall, whether combustible
or non-combustible, may be constructed as shown in
Figure 7.12.
Figure 7.12 Mantel Leg, Surround or Wall Projection (acceptable
on both sides of opening)
Heatilator • Birmingham 42-B Installation Manual • 4059-715 • Rev P • 09/28/15
E. Mantel and Wall Projections
The combustible mantel may have a maximum depth of 12
in. (305 mm). Positioned 22 in. (559 mm) above the open-
ing. Combustible trim pieces that project no more than
1-1/2 in. (38 mm) from the face of the fireplace can be
placed no closer than 6 in. (152 mm) from the top of the
opening.
Combustible Wall
2 x 4 stud wall
Standoffs
Non-combustible
Decorative Facing
such as:
Steel, iron, brick,
tile, concrete, slate,
glass, plasters.
1 1/2 in./38 mm
maximum
Measured from top of fireplace opening
Seal joint with
non-combustible
sealant
Figure 7.13 Mantel Specifications
Combustible
7 ft (2134 mm)
Decorative Facing
base of fireplace
Grid represents
1 in. squares
12 in./305 mm
Mantel
22 in./559 mm
minimum
12 in./305 mm
minimum
6 in./152 mm
minimum
minimum
to ceiling
33