Care, cleaning and maintenance
3.6

Combustion chamber

The FireWIN is equipped with a cleaning interval display. The cleaning request for the combustion chamber and
burner pot is displayed on the FireWIN Klassik and Premium after 500 operating hours, on the FireWIN Exklu-
siv after 750 operating hours and must be reset after cleaning has finished – see section 2.8.1.6. „Boiler clea-
ning – Resetting the cleaning request" .
Do not open the combustion chamber door during operation. Always switch the boiler off first with the
ON/OFF button (Fig. 127) and wait until burnout mode has finished. It is essential to let the boiler cool
down before cleaning.

3.6.1 Baffle plate, thermocontrol sensor

– Open the combustion chamber door, lift the baffle plate at the right and guide it out at an angle, sloping
down to the left – Fig. 128, Removing the baffle plate and fly ash.
– If necessary, remove fly ash from the thermocontrol sensor with a cleaning brush. The thermocontrol sen-
sor is located at the top left of the combustion chamber behind the baffle plate – Fig. 129.
Assembly:
By working through these steps in reverse order.
Fig. 127 Switching off FireWIN
Fig. 129
Cleaning the thermocontrol sensor
(with cleaning brush)
Fig. 128
Removing and cleaning the baffle plate
Thermocontrol sensor