Fitting The Feet To The Heat Exchanger Module; Flue Gas Connection - Viessmann vitocrossal 300 Installation Instructions Manual

Gas fired condensing boiler
Hide thumbs Also See for vitocrossal 300:
Table of Contents

Advertisement

Fitting the feet to the heat exchanger module

2.
3.

Flue gas connection

2-3 x D
A
Flue gas system installation
instructions
1. Wind the anti-vibration feet in as far
as possible.
2. Secure the feet with two screws each
to the l.h. and r.h. side of the heat
exchanger using the top holes.
3. Wind out the feet until the heat
exchanger module is sufficiently sup-
ported.
1.
1. Connect the flue outlet via the short-
est possible run to the chimney stack,
maintaining a slight incline.
Avoid sharp bends.
Flue internal 7: 301 mm
2. Create a resealable test port A.
Ø 10 mm
3. Seal the flue (all flue connections
must be pressure-tight).
9