Biasi RIVA ADVANCE HE M110B.24SM/C Service Manual page 47

Wall hung, fan flue, room sealed, high efficiency gas boiler
Hide thumbs Also See for RIVA ADVANCE HE M110B.24SM/C:
Table of Contents

Advertisement

21
Condensate trap
21.1
Function
The condensate trap A in Fig. 21.1 and Fig. 21.2 allows
the discharge of the condensate via the condensate
drain pipe avoiding in the mean time the escape of
combustion products.
A plastic ball closes the trap outlet in case that the trap
is empty.
A
Fig. 21.1
If the drain pipe is plugged or in any case in which the
condensate isn't correctly evacuated, the condensate
level in the trap rises till it reaches the detection elec-
trode in the combustion chamber thus causing the
boiler lock ---out.
21.2
Check the cleanness of the trap
Unscrew the plug on the bottom of the trap and remove
dirt eventually deposit.
21.3
Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1
Remove the front and left case panels.
2
Disconnect the trap from the draining pipe.
Using pliers, remove the spring B moving it up-
3
wards and remove the flexible pipe C.
4
Unscrew the screw D and remove the trap.
Unscrew the lock ---nut E and separate the trap
5
from its bracket.
6
Reassemble carrying out the removal operations
in reverse order.