Table 12. Defrost Control Board Diagnostic LEDs
DS2
DS1
Green
Red
Condition/Code
Possible Cause(s)
Solution
OFF
OFF
Power problem
No power (24V) to board terminals
1 Check
control
transformer
power
(24V).
R & C or board failure.
2 If power is available
to board and LED(s)
do
not light, replace
board.
Simultaneous
Normal operation
Unit operating
normally
or in stand-
None required.
SLOW Flash
by mode.
Alternating
SLOW
5-minute
anti-short
cycle
Initial power up, safety trip, end of
None required (Jumper TEST pins to override)
Flash
delay
room thermostat
demand.
Simultaneous
Ambient
Sensor Problem
Sensor being detected open or shorted or out of temperature
range. Board will revert to
FAST Flash
time/temperature
defrost operation.
(System will still heat or cool).
Alternating
Coil Sensor Problem
Sensor being detected open or shorted or out of temperature
range. Board will not per-
FAST Flash
form demand
or time/temperature
defrost operation.
(System will still heat or cool).
ON
ON
Circuit Board Failure
doeslndicateSnot
clear,that
boardreplacehaSboard.internal
component
failure. Cycle 24 volt power to board. If code
Table 13. Defrost Control Board Diagnostic Fault and Lockout Codes
DS2
DS1
Green
Red
Condition/Code
Possible Cause(s)
Solution
(Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
OFF
OFF
SLOW
Flash
ON
SLOW
Low Pressure
Fault
Flash
ON
Low Pressure
LOCKOUT
OFF
High Pressure
Fault
OFF
High Pressure
LOCKOUT
1 Restricted air flow over indoor or
outdoor coil.
2 Improper refrigerant charge in
system.
3 Improper metering device
installed or incorrect operation
of metering device.
4 Incorrect or improper sensor
location or connection to sys-
tem.
1 Remove any blockages or restrictions from
coils and/or fans. Check indoor and outdoor
fan motor for proper current draws.
2 Check system charge using approach and
subcooling temperatures.
3 Check system operating pressures and
compare to unit charging charts.
4 Make sure all pressure switches and sensors
have secure connections to system to prevent
refrigerant leaks or errors in pressure and
temperature measurements.
SLOW
ON
Discharge
Line Temperature
Flash
Fault
FAST
Flash
ON
Discharge Line Tempera-
ture LOCKOUT
This code detects shorted
sensor or high discharge
temperatures.
If the discharge
line
temperature
exceeds a temperature
of 300°F (148°C) during compressor
operation,
the
board will de-energize
the compressor
contactor
output (and the defrost output if active).
The compressor
will remain off until the discharge
temperature
has dropped below 225°F
(107°C).
OFF
Fast
Discharge
Sensor Fault
Flash
Fast
OFF
Discharge
Sensor
Flash
LOCKOUT
The board detects open sensor or out of temperature
sensor range. This fault is detected
by allowing
the unit to run for 90 seconds
before checking
sensor resistance.
If the sen-
sor resistance
is not within range after 90 seconds,
the board will count one fault. After 5
faults, the board will lockout.
DETAILED DEFROST SYSTEM OPERATION
The demand defrost control board initiates a defrost cycle
based on either frost detection or time.
Frost Detection--If
the compressor runs longer than 34
minutes and the actual difference between the clear coil
and frosted
coil temperatures
exceeds
the maximum
difference allowed by the control, a defrost cycle will be
initiated.
IMPORTANT-
The demand defrost control board will allow
a greater accumulation
of frost and will initiate fewer
defrost cycles than a time/temperature
defrost system.
Time--If
six hours of heating mode compressor run time
has elapsed since the last defrost cycle while the coil
temperature
remains below
35°F (2°C), the demand
defrost control will initiate a defrost cycle.
Actuation--When
the reversing valve is de-energized,
the Y1 circuit is energized, and the coil temperature
is
below 35°F (2°C), the board logs the compressor run time.
If the board is not calibrated, a defrost cycle will be initiated
after 34 minutes of heating mode compressor
run time,
The control will attempt to self-calibrate after this (and all
other) defrost cycle(s),
505329M
0_08
Page 24