Lennox Elite Series Installation Instructions Manual page 20

Table of Contents

Advertisement

Table 6. XP16-048
Target
INDOOR
HEAT
Subcooling
**Add
MATCHUP
PUMP
Heat
Cool
charge
(+5°F)
(+I°F)
CH23 68
15
13
0
7
CB27UH-048
17
7
0
0
CB27UH-060
17
7
0
0
CB30U 51, 65
17
7
0
0
CBX32M-048, -060
17
7
0
0
CBX32MV-068
16
10
0
3
CH33 60D 2F
18
4
0
2
CH33-62D-2F
15
10
0
4
CR33-60
40
4
0
2
CX34 60D 6F
18
4
0
2
CX34-62D-6F
16
8
0
2
Table 7. XP16-060
Target
INDOOR
HEAT
Subcooling
**Add
MATCHUP
PUMP
Heat
Cool
charge
(+5°F)
(+I°F)
CH23 68
13
14
3
3
CH23-65
18
2
0
0
CBX26UH-060
13
14
3
5
CB27UH-060
13
10
2
1
CBX32M-060
13
10
2
1
CBX32MV-068
13
12
2
9
CH33 60D 2F
15
6
1
3
CH33-62D-2F
13
12
2
10
CR33-50/60C-F
30
6
1
3
CR33 60D F
30
6
1
3
CX34-49C-6F
13
9
1
14
CX34-60D-6F
15
6
1
3
CX34 62C 6F
13
11
2
6
CX34-62D-6F
13
11
2
5
NOTE - Use the tables 8 and 9 to perform maintenance
checks; it is not a procedure for charging the system. Minor
variations in these pressures may be due to differences in
installations. Significant deviations could mean that the
system is not properly charged or that a problem exists
with some component in the system.
Table 8. Normal Operating Pressures - Cooling 1
XP 16
-024
-036
-048
-060
°F (°C) 2
Liq
I Vap
Liq
I Vap
Liq
I Vap
Liq
I Vap
First Stage (Low Capacity) Pressure 3
65 (18.3}
232
146
225
144
235
144
225
138
75 (23.9}
264
148
261
147
268
145
264
141
85 (29.4)
307
149
302
149
310
147
305
142
95 (35.6)
353
151
349
151
356
148
352
146
165 (46.6)
403
153
397
153
407
150
405
148
115(46.1)
460
155
461
157
466
152
459
150
Second Stage (High Capacity)
Pressure 3
65 (18.3)
240
143
239
139
244
140
241
134
75 (23.9)
279
145
278
141
283
141
280
136
85 (29.4)
322
147
322
143
326
144
324
137
95 (35.6)
371
149
367
146
374
147
373
138
165 (46.6)
423
151
426
148
427
148
425
142
115(46.1)
485
154
489
151
491
151
486
146
Table 9. Normal Operating Pressures - Heating 1
XP 16
-024
-036
-048
-060
°F (°C) 2
Liq
I Vap
Liq
I Vap
Liq
I Vap
Liq
I Vap
First Stage (Low Capacity)
Pressure 3
46 (4.4)
337
93
328
98
369
75
351
63
50 (16)
322
117
333
118
366
114
335
92
Second Stage
(High Capacity)
Pressure
3
26 (-7.0)
279
62
296
62
311
58
308
59
36 (-1.6)
288
76
309
75
334
72
323
70
46 (4.4)
302
93
322
92
354
89
318
69
56(16)
306
112
336
113
381
108
329
82
1
Most-popular-match-up
pressures.
Indoor match up, indoor air quality, and indoor load
cause pressures
to vary.
2
Temperature
of the air entering
the outdoor coil.
3
Liquid -+10 & Vapor -+5 psig.
Table 10. HFC-410A Temp. (°F) - Pressure (Psig)
°F
Psig
°F
Psig
°F
Psig
°F
Psig
32
100.8
63
178.5
94
290.8
125
445.9
33
102.9
64
181.6
95
295.1
126
451.8
34
105.0
65
184.3
96
299.4
127
457.6
35
107.1
66
187.7
97
303.8
128
463.5
36
109.2
67
190.9
98
308.2
129
469.5
37
111.4
68
194.1
99
312.7
130
475.6
38
113.6
69
197.3
100
317.2
131
481.6
39
115.8
70
200.6
101
321.8
132
487.8
40
118.0
71
203.9
102
326.4
133
494.0
41
120.3
72
207.2
103
331.0
134
500.2
42
122.6
73
210.6
104
335.7
135
506.5
43
125.0
74
214.0
105
340.5
136
512.9
44
127.3
75
217.4
106
345.3
137
519.3
45
129.7
76
220.9
107
350.1
138
525.8
46
132.2
77
224.4
108
355.0
139
532.4
47
134.6
78
228.0
109
360.0
140
539.0
48
137.1
79
231.6
110
365.0
141
545.6
49
139.6
80
235.3
111
370.0
142
552.3
50
142.2
81
239.0
112
375.1
143
559.1
51
144.8
82
242.7
113
380.2
144
565.9
52
147.4
83
246.5
114
385.4
145
572.8
53
150.1
84
250.3
115
390.7
146
579.8
54
152.8
85
254.1
116
396.0
147
586.8
55
155.5
86
258.0
117
401.3
148
593.8
56
158.2
87
262.0
118
406.7
149
601.0
57
161.0
88
266.0
119
412.2
150
608.1
58
163.9
89
270.0
120
417.7
151
615.4
59
166.7
90
274.1
121
423.2
152
622.7
60
169.6
91
278.2
122
428.8
153
630.1
61
172.6
92
282.3
123
434.5
154
637.5
62
175.4
93
286.5
124
440.2
155
645.0
INSTALLING
SERVICE VALVE CAPS
Disconnect gauge set and re-install both the liquid and
suction service valve caps,
INSTALL CAPS
OUTDOOR
UNIT
/
SERVICE
VALVES_
Figure 35. Installing Service Valve Caps
505329M
04/08
Page 20