Lennox Elite Series Installation Instructions Manual page 18

Table of Contents

Advertisement

have consulted
with the power company and the
voltage condition has been corrected.
6, Set the thermostat for a cooling demand. Turn on
power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate,
8, Check system for sufficient refrigerate by using the
procedures
listed
under
Testing
and
Charging
System,
TESTING AND CHARGING SYSTEM
This system uses HFC-410A refrigerant which operates at
much higher pressures than HCFC-22. The pre-installed
liquid line filter drier is approved for use with HFC-410A
only. Do not replace it with components designed for use
with HCFC-22, This unit is NOT approved for use with coils
which use capillary tubes as a refrigerant metering device.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC-410A,
2, Connect the manifold gauge set to the unit's service
ports as illustrated in figure 2.
low pressure gauge to vapor service port
high pressure gauge to liquid service port
COOLING
MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta-T (DT) process using the
illustration in figure 32,
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:
Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
Measuring voltage supplied to the unit,
Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula
to determine CFM:
CFM =
Amps x Volts x 3.41
1.98 x Temperature
rise (F)
CALCULATING
CHARGE
If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the
unit, To calculate the total refrigerant charge:
Additional charge
Amount
Adjust amount, for
specified per
specified
variation in line set
indoor unit
on
length listed on table
match-up listed in
Total
nameplate
in figure 33.
tables 4 through 7.
charge
+
+
=
Temp.
}
DT
ofair
180
24 24 24 23 23 22 22 22 20 19 18 17 16 15
entering.._178
23 23 23 22 22 21 21 20 19 18 17 16 15 14
indoor _ I _
coilOF
_l.u
22 22 22 21 21 20 19 19 18 17 16 15 14 13
I
_'174
21 21 21 20 19 19 18 17 16 16 15 14 13 12
_[72
20 20 19 18 17 17 16,/_15
14 13 12 11 10
70
19 19 18 18 17 17 16 15 15 14 13 12 11 10
Wet-bulb°F
57 58 59 60 61 62 63 64 65 66 67 68 69 70 [
n
90
DRY
BULB
All temperatures
are
iNDOOR
WET
expressed
in °F
COiL
BULB
Step 1. Determine
the desired DT--Measure
entering air tempera-
ture using dry bulb (A) and wet bulb (B). DT is the intersecting value of
A and B in the table (see triangle).
Step 2. Find temperature
drop across coil--Measure
the coil's dry
bulb entering and leaving air temperatures
(A and C). Temperature
Drop Formula: (TDrop) = A minus C.
Step 3. Determine
if fan needs adjustment--If
the difference be-
tween the measured TDrop and the desired DT (TDropiDT) is within
±3 °, no adjustment is needed, See examples: Assume DT = 15 and A
temp. = 72 °, these C temperatures would necessitate stated actions:
C °
TDrop-
DT
=
°F
ACTION
53°
19
-
15
=
4
Increase the airflow
58°
14
-
15
=
-1
(within +3° range) nochange
62 °
10
-
15
=
-5
Decrease the airflow
Step 4. Adjust the fan speed--See
indoor unit instructions to in-
crease/decrease
fan speed.
Changing air flow affects all temperatures;
recheck temperatures
to
confirm that the temperature drop and DT are within +3 °.
Figure 32. Checking
Indoor Airflow over Evaporator Coil using Delta-T Chart
WEIGH
Refrigerant
Charge
per Line Set Length
Liquid
Line
Ounces
per 5 feet (g per 1.5 m)
Set Diameter
adjust from
15 feet (4.6 m) line set*
3/8" (9.5 mm)
3 ounce
per 5' (85 g per 1.5 m)
NOTE - *If line length is greater than 15 ft. (4.6 m), add this
amount. If line length is less than !5 ft. (4.6 m), subtract this
amount.
LENNOX
_i|m[IWiIiiiHi
1. Check Liquid and suction line pressures
2. Compare unit pressures with tables 8 and
9, Normal Operating Pressures.
3. Conduct
leak
check;
evacuate
as
previously outlined,
4. Weigh in the unit nameplate charge plus
any charge required for line set differences
over feet,
This nameplate is for illustration purposes
only. Go to actual nameplate on outdoor
unit for charge information.
Figure 33. Using Weigh In Method
505329M
04/08
Page 18

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp16 series

Table of Contents