5. Use a field-provided fitting to temporary reconnect the
liquid line to the indoor unit's liquid line orifice housing,
DISTRIBUTOR
TUBES
LIQUID LINE ORIFICE
HOUSING
TEFLON
RING
Remove
and discard
valve
FIXED
stem assembly
(if present)
BRASS NUT
/
" j ....
VA_
?' "%% _'2s_
ASS_
"_T
VALVE STEM C AP
(Uncased
Coil Shown
Figure 20. Typical Fixed Orifice Removal
TYPICAL TXV REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and
plumbing panels,
2. Remove any shipping clamps holding the liquid line
and distributor assembly,
3. Disconnect the equalizer line from the TXV equalizer
line fitting on the suction line,
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
UNCASED
COIL
LIQUID
LINE
STUB END
ONLY)
ORIFICE
HOUSING
DISTRIBUTOR
TXV
TUBES
RING
SENSING
LINE
/
MALE EQUALIZER LINE
/
FITTING
/
SUCTION
SENSING
BULB
L_,
LIQUID
LINE
Figure 21. Typical TXV Removal
4. Remove the suction line sensing bulb.
5. Disconnect the liquid line from the TXV at the liquid line
assembly,
6. Disconnect the TXV from the liquid line orifice housing.
Take care not to twist or damage distributor
tubes
during this process,
7. Remove and discard TXV and the two Teflon rings as
illustrated.
8. Use a field-provided fitting to temporary reconnect the
liquid line to the indoor unit's liquid line orifice housing,
A IMPORTANT
A IMPORTANT
IMPORTANT
CAUTION
505329M
04/08