Electrical Service Guide - Miller Electric XMT 350 CC/CV Owner's Manual

Arc welding power source
Hide thumbs Also See for XMT 350 CC/CV:
Table of Contents

Advertisement

4-5. Electrical Service Guide

NOTICE − INCORRECT INPUT POWER can damage this welding power source. Phase to ground voltage shall not exceed +10% of rated input
voltage.
NOTICE − Actual input voltage should not be 10% less than minimum and/or 10% more than maximum input voltages listed in table. If actual input
voltage is outside this range, output may not be be available.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
2
Time-Delay
3
Normal Operating
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
2
Time-Delay
3
Normal Operating
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 2005 National Electrical Code (NEC) (including article 630)
1 Consult factory for circuit breaker applications.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" (65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
OM-2247 Page 16
1
4
4
1
4
4
Single-Phase
208
230
400
60.8
54.6
29.7
70
60
35
80
80
45
8
8
10
72
89
176
(22)
(27)
(54)
8
8
10
Three-Phase
208
230
400
40.4
36.1
20.6
45
40
25
60
50
30
8
10
12
119
96
175
(36)
(29)
(53)
10
10
12
460
575
25.4
19.9
30
25
40
30
12
12
140
219
(43)
(67)
12
12
460
575
17.8
14.1
20
15
25
20
14
14
150
234
(46)
(71)
14
14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auto-line xmt 350 ccAuto-line xmt 350 cv

Table of Contents