4-8. Stick DCEP (Direct Current Electrode Positive) Connections

4-9. Electrical Service Guide

NOTE
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2005 National Electrical Code (NEC)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
OM-2233 Page 18
2
1
Actual input voltage cannot exceed - 10% of minimum or +10% of maximum input
voltages indicated in table.
1
2
Time Delay
3
Normal Operating
4
4
Y Turn off power before mak-
1
Connect work lead to negative weld
output terminal.
2
Connect electrode holder to posi-
tive weld output terminal.
Single-Phase,
Single-Phase,
100% Duty
60% Duty
Cycle
Cycle
115
230
25
22
25
25
35
30
10
12
57 (17)
79 (24)
10
12
ing connections.
Negative (−) Weld Output
Terminal
Positive (+) Weld Output
Terminal
Ref. 802 888-A
Three-Phase, 60% Duty
Cycle
230
400
460
13.1
7.4
6.4
15
8
8
20
10
10
14
14
14
102
308
407
(31)
(94)
(124)
14
14
14