Boiler Checking & Adjusting; Gas Pressure Adjustment; Boiler Maintenance - Smith GT-150 Installation, Operating And Maintenance Manual

Gt series
Table of Contents

Advertisement

Page 30
BOILER CHECKING
& ADJUSTMENT
Input Rate
Gas appliances are rated based on sea level operation
with no adjustment required at elevations up to 2000 ft,
610 m. At elevations above 2000 ft, 610 m, input ratings
should be reduced by 4% for each 1000 ft, 305 m, above
sea level. Check the input rate as follows:
NATURAL GAS:
1. Turn off all other gas appliances that use the same
gas meter as the boiler.
2. Call the gas company for the gas heating value.
3. Start the boiler and let it run for 15 minutes.
4. Using the gas meter and a stopwatch, clock the time
that it takes to burn 10 cubic feet of gas and divide
the time by 10.
5. Insert the heating value and the time, in seconds,
into the formula below.
Input Rate = Heating Value(Btu/ft
Flow Rate(s/ft
EXAMPLE: If the heating value = 1000 Btu/ft
and the fl ow rate
Input Rate = (1000 Btu/ft
18 s/ft
Input Rate = 200,000 Btu/hr
If the computed rate deviates by more than 5% from the
rated input value of the unit adjust the gas valve pressure
according to the GAS PRESSURE ADJUSTMENT
instructions that follow.
PROPANE GAS:
The input rate for LP units is factory set based on the
orifi ce size. Use a combustion analyzer to ensure that
the CO
reading falls between 9% and 10.5% with a CO
2
reading of less than 175 ppm air free.
CAUTION: Never increase the input to the boiler
above that for which it is rated. Doing so can cause
premature failure of the boiler!

Gas Pressure Adjustment

Optimum results are obtained when the boiler is operated
at its full input rating. If adjustment is necessary the
following steps must be followed:
1. Connect a fl ue gas analyzer to the vent pipe.
2. Rotate the input adjustment screw clockwise to
decrease the manifold pressure, counterclockwise to
increase it, Figure 41. Never force the input adjustment
screw or the gas valve will be damaged!
GT INSTALLATION AND OPERATION INSTRUCTIONS
3
)(3600 s/hr)
3
)
3
= 18 s/ft
3
3
)(3600 s/hr)
3
3. For natural gas the CO
8% and 9.5% with a CO reading of less than 175
ppm air free. For LP gas the CO
between 9% and 10.5% with a CO reading of less
than 175 ppm air free.
Main Burner Flame
A properly adjusted main burner fl ame will produce a
tight blue fl ame pattern about 1/2 in, 13 mm, tall from
the burner's surface, Figure 43. A yellow fl oating or tall
stringy fl ame is not normal and must be corrected.
WARNING: Yellow, fl oating fl ames indicate a lack
of combustion air. DO NOT operate the boiler until
the problem is solved or severe personal injury
or death may occur!
Figure 43 - Burner Flame
Thermostat Adjustment
Set the heat anticipator to 1.1 amps when controlling
the boiler directly. For zoned systems set the heat
anticipator to match the amp draw of the zone valves or
pump relays.

BOILER MAINTENANCE

The boiler should be cleaned and inspected once a year,
before each heating season.
CAUTION: Servicing, inspection and adjustment
must be done by a trained technician in accordance
with all applicable local and national codes. Improper
servicing or adjustment could damage the boiler!
Controls
Use a soft brush and/or a vacuum cleaner to ensure that
the electrical components are free from dust or deposits
that would impair the boiler's performance.
reading should fall between
2
reading should fall
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt-200Pgt-150Pgt-200

Table of Contents