Steam or water heating pressurized for firing oil, gas or combination gas/oil (13 pages)
Summary of Contents for Smith 70-195
Page 1
GBXIOM-4 00-GBXIOM Gas-Fired Residental Boilers Models 70-195 – Water Only Boiler Manual Installation and Operation Instructions This manual is intended only for use by a qualified heating installer/technician. Read and follow this manual, all supplements and related instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in these in- structions.
INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE A. INSTALLATION SEQUENCE ..... . .2 Follow the installation instructions provided in this B.
INSTALLATION AND OPERATING INSTRUCTIONS 1. PREINSTALLATION Read carefully, study these instructions before beginning work. This boiler must be installed by a qualified contractor. The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly. NOTICE The equipment must be installed in accordance with those installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code , ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code .
INSTALLATION AND OPERATING INSTRUCTIONS 3. Indoor Air Opening Size and Location: Openings C. AIR FOR COMBUSTION AND connecting indoor spaces shall be sized and located VENTILATION as follows: a. Combining spaces on the same floor: 1. Adequate combustion air and ventilation air must be Provide two permanent openings communicating provided for this appliance in accordance with the with additional spaces that have a minimum free...
Page 5
INSTALLATION AND OPERATING INSTRUCTIONS 4. Outdoor Combustion Air: Outdoor combustion air is ii. Where communicating with the outdoors to be provided through one or two permanent through horizontal ducts, each opening shall openings. The minimum dimension of these air have a minimum free area of 1 in per 2000 openings is 3 inches (76 mm).
INSTALLATION AND OPERATING INSTRUCTIONS 5. Combination Indoor and Outdoor Combustion Air: If iii. Nonmotorized dampers shall be fixed in the the required volume of indoor air exceeds the open position. available indoor air volume, outdoor air openings or ducts may be used to supplement the available b.
INSTALLATION AND OPERATING INSTRUCTIONS 2. BOILER SET-UP 1. Provide a sound, level foundation. Locate boiler as 4. Separate the wood shipping pallet from the boiler near to the chimney or outside wall as possible and base by removing two (2) hold-down bolts at each centralized with respect to the heating system.
INSTALLATION AND OPERATING INSTRUCTIONS 5. Install this boiler so that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacements, etc.). 6. If this boiler and distribution system is used in conjunction with a refrigeration system, pipe the chilled medium in parallel with the boiler and install the proper valve to prevent the chilled medium from...
INSTALLATION AND OPERATING INSTRUCTIONS C. PIPING FOR ZONED SYSTEMS 1. See Figures 3.5 and 3.6 for basic zoned system layouts. 2. Run each zone pipe down then up to zone to prevent air accumulation in piping. 3. If required, provide means to isolate and drain each zone separately.
INSTALLATION AND OPERATING INSTRUCTIONS D. EXPANSION TANK FREEZE PROTECTION For new or existing systems that must be freeze- 1. Consult the tank manufacturer’s instructions for protected: specific information relating to tank installation. Size the expansion tank for the required system volume WARNING and capacity.
INSTALLATION AND OPERATING INSTRUCTIONS 4. VENTING A. INTEGRAL DRAFT HOOD B. VENT DAMPER INSTALLATION – GENERAL 1. The boiler is equipped with a built-in draft hood. This device is designed to: 1. Do not use one vent damper to control two or more heating appliances.
INSTALLATION AND OPERATING INSTRUCTIONS 4. Before connection of joints, inspect the vent pipe C. VENT PIPING AND CHIMNEY interior for foreign objects such as tools, equipment, rags, etc. and remove if present. 1. Install vent piping in accordance with Venting of Equipment part of the National Fuel Gas Code, 5.
INSTALLATION AND OPERATING INSTRUCTIONS d. Place in operation the appliance being inspected. D. BOILER REMOVAL FROM COMMON Follow the lighting instructions. Adjust thermostat so VENTING SYSTEM appliance will operate continuously. At the time of removal of an existing boiler, follow these Mettre en service l’appareil à...
INSTALLATION AND OPERATING INSTRUCTIONS 5. GAS PIPING 1. Size and install the gas supply piping properly in order to provide a supply of gas sufficient to meet the maximum demand without undue loss of pressure between the meter and the boiler. 2.
Page 15
INSTALLATION AND OPERATING INSTRUCTIONS Table 5.1: Natural Gas Input Size Cubic Feet / Hour Cubic Meters / Hour Table 5.2: LP Gas Input Size Cubic Feet / Hour Cubic Meters / Hour Table 5.4: Pipe Capacity Capacity of pipe of different diameters and lengths in cubic feet per hour [cubic meter per hour] with a pressure drop of 0.3 inches of water (75 Pa) and specific gravity of 0.60.
INSTALLATION AND OPERATING INSTRUCTIONS 6. ELECTRICAL Install all electrical wiring in accordance with the National Electrical Code and local requirements. NOTICE This unit when installed must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the current edition of the National Electrical Code , ANSI/NFPA 70 and/or the Canadian Electrical Code , Part 1 CSA C22.1, Electrical Code.
Page 17
INSTALLATION AND OPERATING INSTRUCTIONS...
Page 18
INSTALLATION AND OPERATING INSTRUCTIONS...
INSTALLATION AND OPERATING INSTRUCTIONS 7. START-UP PROCEDURES A. COMPLETING THE INSTALLATION 1. Confirm that all water, gas and electricity are turned off. 2. Inspect the boiler combustion chamber for foreign objects and remove if present. 3. Check physical condition of burners and pilot. Make certain that there are no unusual bends or perforations in the burners or pilot.
Page 21
INSTALLATION AND OPERATING INSTRUCTIONS Figure 7.3: Operating Instructions...
Page 22
INSTALLATION AND OPERATING INSTRUCTIONS Figure 7.4: Operating Instructions...
INSTALLATION AND OPERATING INSTRUCTIONS B. CONTROL DESCRIPTIONS D. CHECKING BURNER INPUT See Figure 6.1 in Section 6 (Electrical) for locations of 1. Refer to rating label mounted on the jacket top panel these devices. to obtain the rated BTU per hour input. In no case shall the input to the boiler exceed the value shown 1.
INSTALLATION AND OPERATING INSTRUCTIONS Table 7.1b: Meter Conversion – Natural Gas 3. Low Water Cut-Off (if used) – Consult the (SI Metric Units) manufacturer’s instructions for the low water cut-off operational check procedure. Burner inputs in kW for for various meter timings and heat values.
INSTALLATION AND OPERATING INSTRUCTIONS 8. TROUBLESHOOTING DANGER A. SHUT-DOWN CAUSED BY PILOT OUTAGE, BLOCKED VENT SHUT-OFF When servicing or replacing items that communicate SWITCH OR FLAME ROLL-OUT SAFETY with the boiler water, be certain that: SHUT-OFF SWITCH There is no pressure on the boiler. In the event of a shut-down caused by a pilot outage, The boiler is not hot.
Page 26
INSTALLATION AND OPERATING INSTRUCTIONS Table 8.1: Boiler Troubleshooting Guide PROBLEM POSSIBLE CAUSES CORRECTIVE ACTIONS Burners not functioning. 1. No power. 1. Check line voltage wiring and fuses. 2. Limit not working. 2. Check wiring and contacts, relay, temperature setting. Clean and adjust as necessary. 3.
Page 27
INSTALLATION AND OPERATING INSTRUCTIONS START BEFORE TROUBLESHOOTING, NOTE: “CALL FOR HEAT” 24 VAC SUPPLY IS CONNECTED TO THE 24 V TERMINAL ON THE CONTROL. FAMILIARIZE YOURSELF WITH THE STARTUP AND CHECKOUT PROCEDURES. TURN GAS SUPPLY OFF, TURN THERMOSTAT (CONTROLLER) TO “CALL FOR HEAT.”...
INSTALLATION AND OPERATING INSTRUCTIONS 9. MAINTENANCE WARNING Product Safety Information Refractory Ceramic Fiber Product This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F (980°C), they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans.
INSTALLATION AND OPERATING INSTRUCTIONS A. GENERAL D. MONTHLY (WITH BOILER IN USE) 1. Disconnect this boiler from the gas supply piping 1. Check boiler room floor drains for proper during any pressure testing of the gas system. functioning. 2. Check pipes adjacent to cold walls or in unheated 2.
Page 30
INSTALLATION AND OPERATING INSTRUCTIONS c. Remove burners and brush orifice spuds lightly using a soft bristle brush. d. Remove the vent pipe, vent damper, top jacket panels and flue collector/draft diverter. e. Brush flueways with wire brush. f. To the extent possible, inspect inside of vent pipe and vent damper for obstructions in flow or vent damper movement.
INSTALLATION AND OPERATING INSTRUCTIONS 11. REPAIR PARTS REPAIR PARTS Note: Remember to include boiler model number and serial number when ordering parts. Figure 11.1: Base/Combustible Floor Pan Table 11.1: Base/Combustible Floor Pan Quantity Stock Description Required Code Base Assembly – 70 –...