Photoelectric smoke/heat detectors
Hide thumbs Also See for F220 Series:
Table of Contents

Advertisement

F220 Series | Installation Instructions | 1.0
2. When the LED flashes red, place the magnet near
the "T" again.
3. Hold the magnet against the "T" on the detector
base until the green LED flashes twice and the red
LED repeats the sensitivity indication. This turns
on the CleanMe feature.
4. The LED flash sequence is as follows:
a.
single flash green LED
b.
double flash green LED
5. To disable CleanMe, repeat this process and verify
the double flash returns to a single flash.
1.6

Magnet operation/sensitivity mode

The F220P Series Detectors feature a unique magnet
operation/sensitivity test. Test the detector by placing
the magnet next to the "T" marked on the detector
base for three consecutive flashes to cause an alarm. If
the magnet is there for less than three flashes and more
than one flash, the detector goes into Sensitivity Mode.
Table 2 describes the different LED flash rates for the
Sensitivity Mode.
Table 2: Red LED flash definition
# of Red
Definition
Flashes
1
Malfunctioning smoke or heat detector
3
Normally operating smoke or heat detector
with little or no dirt contamination
4 to 6
Progressively more contamination
7 to 10
Trouble condition, very dirty but still
compensated to 3%. < 3% at 10 flashes.
11
< 2.5%/ft (2.5%/0.3 m)
12
< 2.0%/ft (2.0%/0.3 m), chance of false
alarm increased
13
< 1.5%/ft (1.5%/0.3 m)
14
< 1.0%/ft (1.0%/0.3 m), chance of false
alarm greatly increased
15
< 0.5%/ft (0.5%/0.3 m), false alarm very
likely
1.6.1

The LED sensitivity flash procedure

1. Briefly place the magnet at the "T" on the detector
base for at least one red LED flash but less then
three LED flashes.
2. Wait for the first single green LED flash.
3. Count the number of red LED flashes that follow.
This indicates the sensitivity.
Bosch Security Systems | 8/05 | 4998138694D
General Information
1.6.2
Normal sensitivity LED flash example (see
Figure 2)
1. Enter Sensitivity Mode on the smoke detector.
2. The LED flash sequence is as follows:
a.
three red LED flashes
b.
a single green LED flash (a separator)
c.
three red LED flashes
d.
a single green LED flash.
3. The detector exits sensitivity mode and returns to
one green LED flash every eight seconds.
Figure 2:
1
1 - Green LED flash
2 - Sequence of three red LED flashes
3 - Green LED flash to leave sensitivity mode
4 - 8 seconds later
5 - Green LED flash to return to normal operation
1.6.3
Normal CleanMe sensitivity LED flash
procedure
1. Briefly place the magnet at the "T" on the detector
base for at least one red LED flash but less than
three red LED flashes.
2. Wait for the LED to flash green three times.
3. Count the number of red LED flashes that follow.
This indicates the sensitivity.
1.6.4
The CleanMe sensitivity LED flash example
1. Enter Sensitivity Mode on the smoke detector.
2. The LED flash sequence is as follows:
a.
three red LED flashes
b.
three green LED flashes (a separator)
c.
three red LED flashes
d.
two green LED flashes.
3. The detector exits the sensitivity mode and shows
two green LED flashes every eight seconds.
LED flashes for normal operation
EN | 3