Test Run - Toshiba MMU-AP0094HP-E Installation Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
+001114119501.book Page 43 Wednesday, October 17, 2012 8:23 PM
 Locking the louvers
(No swing)
1. Push
(right side of the button) for 4 seconds
or more when the air conditioner is not working.
flashes.
Indicates CODE No. [F1].
2. Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit numbers
change as follows:
The fan of the selected unit runs and the louvers
start swinging.
UNIT No.
UNIT No.
UNIT No.
1-1
1-2
1-3
UNIT No.
1-4
3. Select a louver you want to lock by pushing "TEMP."
buttons.
4. Select the wind direction of the louver you do not
want to swing by pushing "TIME"
buttons.
(1)
(2)
(3)
SET DATA
0001
0002
0003
(4)
(5)
0004
0005
* When (4) or (5) is selected, dew drop may occur
during cooling mode.
5. Determine the setting by pushing
button.
When the setting has been determined,
lights
up.
6. Push
button to complete the setting.
0001-0005
(Louver lock position code)
85-EN
 Cancelling louver lock
Set the wind direction to "0000" of the louver lock setup
procedure above.
Setting data
0000
• When the setting is canceled,
goes out.
Other operations are the same as those in
"Locking the louvers (No swing)".
 Group control
In a group control, a remote controller can control up to
maximum 8 units.
• For wiring procedure and wiring method of the
individual line (Identical refrigerant line) system,
refer to "Electric work" in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
Connect the indoor units by connecting the remote
controller inter-unit wires from the remote controller
terminal blocks (A/B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A/B) of the other indoor unit.
(Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
 Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor
to sense the temperature around the remote controller.
Select items following the basic operation procedure
1
2
3
4
5
6
(
).
3
• Specify [32] for the CODE No. in Procedure
.
• Select the following data for the SET DATA in
4
Procedure
.
SET DATA
0000
0001
Remote controller
Not used
Used
sensor
(factory default)
When
flashes, the remote controller sensor is
defective.
Select the SET DATA [0000] (not used) or replace the
remote controller.
– 43 –
9

Test run

 Before test run
• Before turning on the power supply, carry out the
following procedure.
1) Using 500 V-megger, check that resistance of
1 MΩ or more exists between the terminal block of
the power supply and the earth (grounding).
If resistance of less than 1 MΩ is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more be for operating.
• Never press the electromagnetic contactor to forcibly
perform a test run. (This is very dangerous because
the protective device does not work.)
• Before starting a test run, be sure to set addresses
following the installation manual supplied with the
outdoor unit.
 Executing a test run
Using the remote controller, operate the unit as usual.
For the procedure of the operation, refer to the
attached Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by thermo.-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
◆ In case of wired remote controller
2, 4
3
1,5
1
Keep
button pushed for 4 seconds or
more. [TEST] is displayed on the display part
and the selection of mode in the test mode is
permitted.
2
Push
button.
3
Using
button, select the operation
mode, [
Cool] or [
Heat].
• Do not run the air conditioner in a mode other
than [
Cool] or [
Heat].
• The temperature controlling function does not
work during test run.
• The detection of error is performed as usual.
4
After the test run, push
button to
stop a test run.
1
(Display part is same as procedure
.)
5
Push
check button to cancel (release
from) the test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
86-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents