Refrigerant Pipe Length
Single
Allowable pipe length (m)
Total length L
75
Pipe diameter (mm)
Gas side
Ø15.9
Simultaneous twin (SP140 type only)
Allowable pipe length (m)
Distributed
Total length
Distributed
pipes
1 +
2
pipes
2
1 +
3
3
Maximum
Maximum
Maximum
50
15
Pipe diameter (mm)
Main pipe
Gas side
Liquid side
Ø15.9
Ø9.5
Figure of Single
Indoor Unit
Outdoor Unit
EN-15
Height difference (Indoor-outdoor H) (m)
Indoor unit: Upper
Outdoor unit: Lower
30
Number of bent portions
Liquid side
Ø9.5
Height difference (m)
Indoor-outdoor H
Indoor unit:
Outdoor unit:
3 –
2
Upper
Upper
10
30
30
Branching pipe
Gas side
Liquid side
Ø15.9
Ø9.5
Figure of Simultaneous twin
Indoor Unit
Indoor Unit
Distributor
Outdoor Unit
3
2
1
6

AIR PURGING

Airtight test
Before starting an airtight test, further tighten the spindle
valves on the gas side and liquid side.
Pressurize the pipe with nitrogen gas charged from the
30
service port to the design pressure (4.15 Mpa) to
conduct the airtight test.
After the airtight test is completed, evacuate the nitrogen
gas.
10 or less
Air Purge
With respect to the preservation of the terrestrial
environment, adopt "Vacuum pump" to purge air
(Evacuate air in the connecting pipes) when installing the
unit.
• Do not discharge the refrigerant gas to the
Indoor-indoor
atmosphere to preserve the terrestrial environment.
Δ
(
h)
• Use a vacuum pump to discharge the air (nitrogen,
etc.) that remains in the set. If air remains, the capacity
may decrease.
0.5
For the vacuum pump, be sure to use one with a
backflow preventer so that the oil in the pump does not
backflow into the pipe of the air conditioner when the
pump stops.
Number of bent
(If oil in the vacuum pump is put in an air conditioner
portions
including R410A, it may cause trouble with the
refrigeration cycle.)
10 or less
Compound
pressure gauge
–101 kPa
(–76 cmHg)
Handle Low
Charge hose
(For R410A only)
Charge port
(Valve core
(Setting pin))
- 8 -
Vacuum pump
As shown in the figure, connect the charge hose after
Attach the connecting port of the charge hose with a
projection to push the valve core (setting pin) to the
Loosen the flare nut of the packed valve (Gas side) a
Execute vacuuming until the compound pressure
Pressure gauge
Gauge manifold valve
Handle High
(Keep fully closed)
Leave the vacuum pump as it is for 1 or 2 minutes, and
check that the indicator of the compound pressure
Charge hose
(For R410A only)
Vacuum pump
adapter for counter-
flow prevention
(For R410A only)
Vacuum
pump
Disconnect the charge hose from the charge port.
Packed valve at gas side
Tighten the valve and caps of the charge port securely.
the manifold valve is closed completely.
charge port of the set.
Open Handle Low fully.
Turn ON the vacuum pump (*1)
little to check that the air passes through. (*2)
Retighten the flare nut.
gauge indicates –101 kPa (–76 cmHg). (*1)
Close Handle Low completely.
Turn OFF the vacuum pump.
gauge does not return.
Open the valve stem or valve handle fully.
(First, at liquid side, then gas side)
EN-16