2)
Consider the wind direction during the
operational season of the air conditioner, and
install the unit so that the discharge port is set
at a right angle relative to the wind direction.
Strong wind
Strong wind
• When using an air conditioner under low outside
temperature conditions (Outside temp:-5 °C or
lower) in COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
<Example>
Wind shield
Wind shield
Wind shield
EN-9
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1.
Single unit installation
2.
Obstacles on both right and left sides.
The height of the
obstacle should
be lower than
the height of the
outdoor unit.
150 or
300 or
more
more
3.
Serial installation of two or more units
150 or
300 or
300 or
300 or
more
more
more
more
The height of the obstacle should be
lower than the height of the outdoor unit.
Obstacle also above unit
150 or
more
- 5 -
Obstacle in front
Above unit is free
1.
Single unit installation
2.
Serial installation of two or more units
Obstacle also at the above unit
1,000 or
more
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1.
Single unit installation
2.
Serial installation of two or more units
300 or
300 or
more
more
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
1,000 or
300 or
1,500 or
2,000 or
200 or
more
more
more
more
more
EN-10