Installation of Outdoor Unit
• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
Drain hole
525
150
600
Drain hole
Drain nipple
mounting hole
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support the
bottom surface of the fixing leg that is in contact with
and underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
GOOD
Absorb vibration
with vibration-proof
rubber pads
Fixing leg
Foundation
GOOD
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of the fixing leg
that is in contact with and underneath the
bottom plate of the outdoor unit.
NO GOOD
If only the
Do not support
end of the
the outdoor
fixing leg is
unit only with
supported, it
the fixing leg.
may deform.
Foundation
EN-11
Set the out margin of the anchor bolt to 15 mm or less.
• When water is to be drained through the drain hose,
attach the following drain nipple and waterproof rubber
cap, and use the drain hose (Inner diam: 16 mm) sold
on the market. Also seal the knockout hole and screws
securely with silicone material, etc., to prevent water
150
from leaking.
Some conditions may cause dewing or dripping of
water.
• When collectively draining discharged water
completely, use a drain pan.
Waterproof rubber cap
Drain nipple
Waterproof rubber cap
Knockout hole
For Reference
If a heating operation is to be continuously performed for
a long time under the condition that the outdoor
temperature is 0 °C or lower, draining defrosted water
may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally in order to safely install the air conditioner.
For details, contact the dealer.
5

REFRIGERANT PIPING

15 or less
Knockout of Pipe Cover
Knockout procedure
(5pcs.)
Front direction
• The indoor/outdoor connecting pipes can be
connected in 4 directions.
Drain nipple
Take off the knockout part of the pipe cover through
which pipes or wires will pass through the base plate.
• Detach the pipe cover and tap on the knockout section
a few times with the shank of a screwdriver.
A knockout hole can easily be punched.
• After punching out the knockout hole, remove burrs
from the hole and then install the supplied protective
bush and guard material around the passage hole to
protect wires and pipes.
Be sure to attach the pipe covers after pipes have
been connected. Cut the slits under the pipe covers to
facilitate the installation.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
- 6 -
* Be sure to wear heavy work gloves while working.
Rear direction
Pipe cover
Side direction
Down direction
Optional Installation Parts
(Locally procured)
Refrigerant piping
A
Liquid side : Ø9.5 mm
Gas side : Ø15.9 mm
Pipe insulating material
B
(polyethylene foam, 10 mm thick)
C
Putty, PVC tape
Supplied protective bush
Supplied passage hole
guard material
* Attach the guard material
securely so that it does
not come loose.
Parts name
Q'ty
One each
1
One each
EN-12