Introduction; Water - UTICA BOILERS SFH-3085 Installation, Operation & Maintenance Manual

Starfire iv series 4 water oil fired cast iron boiler
Table of Contents

Advertisement

WARNING
!
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious
injury.
• Installation must conform to requirements of the
authority having jurisdiction. Such applicable
requirements take precedence over the general
instructions of this manual.
• Where required by the authority having jurisdiction,
the installation must conform to the American Society
of Mechanical Engineers Safety Code for Controls and
Safety Devices for Automatically Fired Boilers, ANSI/
ASME No. CSD-1.
• LOCATE BOILERS in front of fi nal position before
removing crate. Provide a level solid base as near the
chimney as possible, and centrally located with respect
to the heat distribution system as practical.
• When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to permit

INTRODUCTION

replacement of another appliance such as water heater.
Fire hazard. Do not install boiler on combustible
fl ooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
Boiler must not be installed on carpeting or vinyl fl ooring.
Minimum clearances to combustible construction are:
TOP .......................................... 24 IN.
FRONT ...................................... 24 IN.
FLUE CONNECTOR ........................ 9 IN.
REAR .......................................... 6 IN.
SIDES ......................................... 6 IN.
Clearance for access should exceed fi re protection
clearance.
REMOVE CRATE and plastic protective wrapper, inspect for
damage.
Move boiler to permanent position by sliding or walking.