9.0 Input and Output Ports

Refer to the appropriate Installation
Supplement included with your product
for the specifics of your particular
installation.
Figure 11: D6600 Back Panel Showing
Input/Output Ports
Bosch Security Systems
Fairport, NY
USA
B
A
T
T
E
R
Y
Input:
100 - 120/
220 - 240V~
50 - 60 Hz
2.5 Amps
1 – Input 1
2 – Input 2
3 – Output 2
Figure 12: D6100i Back Panel Showing
Input/Output Ports
1
2
6
5
1 – Ground 2
2 – Input 2
3 – Output 2
Bosch Security Systems, Inc. | 6/09 | 4998122704-06
Conettix D6600/D6100i | Installation and Operation Guide | 9.0 Input and Output Ports
1
2
1
2
6
3
3
4
5
4
4 – Ground 2
5 – Ground 1
6 – Output 1
3
1
2
4
4 – Output 1
5 – Input 1
6 – Ground 1
9.1
UPS Monitoring through CPU
Programmable Input Ports
Use the CPU programmable input port to connect the
external UPS to the D6600/D6100i for power
monitoring. Connect the monitoring port from the UPS
to matching pins on the D6600/D6100i CPU
Programmable Input/Output port (Figure 11). Set up
the D6600/D6100i from Menu 2.2.27 CPU
Programmable Input 1 for Input 1; Menu 2.2.28
CPU Programmable Input 2 for Input 2. Refer to the
D6600/D6100i Program Entry Guide
(P/N: 4998122702) for more information.
9.1.1

Input Default Connection Configuration

The I/O ports work with dry contact outputs.
The open circuit input voltage on the input
measures between 9 V and 12 V.
UPS Battery OK (restore) – contacts closed
UPS Battery Low input – contacts open
You can apply other output sources to the input wiring
as long as you follow these guidelines:
The maximum input voltage allowed without
causing damage to the input is 24 VDC.
For UPS "Battery OK" (restore), the input range
must be between 0 V and 1 V.
For UPS "Battery Low," the input range must be
between 3 V and 24 V.
The programmable input voltage range
is undefined for input voltages between
1 V and 3 V. This might cause
unexpected results such as toggling
between "Battery Low" and "Battery
OK." The input should be connected to
logic level outputs.
13