Ground (1 A), Neutral, And Differential Current Accuracy; Neutral Voltage (Fundamental) Accuracy - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

7.2 HARDWARE FUNCTIONAL TESTS
The specification for neutral, differential and 1 A ground current input accuracy is ±0.5% of 2 × CT. Perform the steps below
to verify accuracy.
1.
Alter the following setpoints:
S2 SYSTEM SETUP
S2 SYSTEM SETUP
S2 SYSTEM SETUP
S5 CURRENT ELEMENTS
S5 CURRENT ELEMENTS
2.
Note: the last two setpoints are needed to view the neutral and the differential current. The trip element will operate
when differential current exceeds 100 A.
Measured values should be ±10 A. Inject (I
3.
accuracy of the measured values. View the measured values in:
A2 METERING DATA
or press the
NEXT
Table 7–1: NEUTRAL AND GROUND CURRENT TEST RESULTS
INJECTED
CURRENT
1 A UNIT
0.1 A
0.2 A
0.5 A
1 A
Table 7–2: DIFFERENTIAL CURRENT TEST RESULTS
INJECTED
CURRENT
0.1 A
0.2 A
0.5 A
7
1 A
The specification for neutral voltage (fundamental) accuracy is ±0.5% of full scale (100 V). Perform the steps below to verify
accuracy.
1.
Alter the following setpoints:
S2 SYSTEM SETUP
S2 SYSTEM SETUP
S2 SYSTEM SETUP
2.
Measured values should be ±5.0 V. Apply the voltage values shown in the table and verify accuracy of the measured
values. View the measured values in:
A2 METERING DATA
APPLIED NEUTRAL
VOLTAGE AT 60 HZ
10 V
30 V
50 V
7-4

7.2.3 GROUND (1 A), NEUTRAL, AND DIFFERENTIAL CURRENT ACCURACY

CURRENT SENSING
GROUND CT:
CURRENT SENSING
GROUND CT RATIO:
CURRENT SENSING
PHASE CT PRIMARY:
PHASE DIFFERENTIAL
PHASE DIFFERENTIAL
only) the values shown in the table below into one phase only and verify
A
CURRENT METERING
key to view the current values when differential trip element is active.
EXPECTED
MEASURED
CURRENT
GROUND
READING
CURRENT
100 A
200 A
500 A
1000 A
EXPECTED CURRENT READING
DIFF. PHASE A
DIFF PHASE B,C
200 A
100 A
400 A
200 A
1000 A
500 A
2000 A
1000 A
VOLTAGE SENSING
NEUTRAL VOLTAGE TRANSFORMER:
VOLTAGE SENSING
NEUTRAL V.T. RATIO:
GEN. PARAMETERS
GENERATOR NOMINAL FREQUENCY:
VOLTAGE METERING
EXPECTED NEUTRAL
VOLTAGE
100 V
300 V
500 V
489 Generator Management Relay
"1A Secondary"
"1000:1"
"1000 A"
"Unlatched"
PHASE DIFFERENTIAL TRIP:
DIFFERENTIAL TRIP MIN. PICKUP:
MEASURED NEUTRAL CURRENT
PHASE A
MEASURED DIFFERENTIAL CURRENT
PHASE A

7.2.4 NEUTRAL VOLTAGE (FUNDAMENTAL) ACCURACY

"Yes"
"10.00:1"
"60 Hz"
MEASURED NEUTRAL
VOLTAGE
7 TESTING