5 ACTUAL VALUES
Flash messages are warning, error, or general information messages that are temporarily displayed in response to certain
key presses. These messages are intended to assist with navigation of the 489 messages by explaining what has hap-
pened or by prompting the user to perform certain actions.
Table 5–2: FLASH MESSAGES
NEW SETPOINT HAS
ROUNDED SETPOINT
BEEN STORED
HAS BEEN STORED
INVALID PASSCODE
NEW PASSCODE
ENTERED!
HAS BEEN ACCEPTED
SETPOINT ACCESS IS
DATE ENTRY WAS
NOW RESTRICTED
NOT COMPLETE
NO TRIPS OR ALARMS
RESET PERFORMED
TO RESET
SUCCESSFULLY
DEFAULT MESSAGE
DEFAULT MESSAGE
HAS BEEN ADDED
LIST IS FULL
INVALID SERVICE CODE
KEY PRESSED IS
ENTERED
INVALID HERE
END OF PAGE
TOP OF LIST
THIS PARAMETER IS
THAT INPUT ALREADY
ALREADY ASSIGNED
USED FOR TACHOMETER
NEW SETPOINT HAS BEEN STORED: This message appear each time a setpoint has been altered and stored as
shown on the display.
ROUNDED SETPOINT HAS BEEN STORED: Since the 489 has a numeric keypad, an entered setpoint value may fall
between valid setpoint values. The 489 detects this condition and store a value rounded to the nearest valid setpoint
value. To find the valid range and step for a given setpoint, press the
OUT OF RANGE! ENTER: #### TO ##### BY #: If a setpoint value outside the acceptable range of values is entered,
the 489 displays this message and substitutes proper values for that setpoint. An appropriate value may then be
entered.
ACCESS DENIED, SHORT ACCESS SWITCH: The Access Switch must be shorted to store any setpoint values. If
this message appears and it is necessary to change a setpoint, short the Access terminals C1 and C2.
ACCESS DENIED, ENTER PASSCODE: The 489 has a passcode security feature. If this feature is enabled, not only
must the Access Switch terminals be shorted, but a valid passcode must also be entered. If the correct passcode has
been lost or forgotten, contact the factory with the encrypted access code. All passcode features may be found in the
S1 489 SETUP
PASSCODE
INVALID PASSCODE ENTERED: This flash message appears if an invalid passcode is entered for the passcode
security feature.
NEW PASSCODE HAS BEEN ACCEPTED: This message will appear as an acknowledge that the new passcode has
been accepted when changing the passcode for the passcode security feature.
PASSCODE SECURITY NOT ENABLED, ENTER 0: The passcode security feature is disabled whenever the pass-
code is zero (factory default). Any attempts to enter a passcode when the feature is disabled results in this flash mes-
sage, prompting the user to enter "0" as the passcode. When this has been done, the feature may be enabled by
entering a non-zero passcode.
ENTER A NEW PASSCODE FOR ACCESS: The passcode security feature is disabled if the passcode is zero. If the
CHANGE PASSCODE SETPOINT
passcode and enable the passcode security feature.
SETPOINT ACCESS IS NOW PERMITTED: Any time the passcode security feature is enabled and a valid passcode
is entered, this flash message appears to notify that setpoints may now be altered and stored.
GE Multilin
OUT OF RANGE.! ENTER:
#### TO ##### BY #
PASSCODE SECURITY
NOT ENABLED, ENTER 0
DATE ENTRY
OUT OF RANGE
ALL POSSIBLE RESETS
HAVE BEEN PERFORMED
PRESS [ENTER] TO
REMOVE MESSAGE
DATA CLEARED
SUCCESSFULLY
END OF LIST
TACHOMETER MUST USE
INPUT 4, 5, 6, OR 7
setpoints menu.
is entered as yes, this flash message appears prompting the user to enter a non-zero
489 Generator Management Relay
5.8 DIAGNOSTICS

5.8.2 FLASH MESSAGES

ACCESS DENIED,
ACCESS DENIED,
SHORT ACCESS SWITCH
ENTER PASSCODE
ENTER A NEW
SETPOINT ACCESS IS
PASSCODE FOR ACCESS
NOW PERMITTED
TIME ENTRY WAS
TIME ENTRY
NOT COMPLETE
OUT OF RANGE
ARE YOU SURE? PRESS
PRESS [ENTER] TO ADD
[ENTER] TO VERIFY
DEFAULT MESSAGE
DEFAULT MESSAGE
DEFAULT MESSAGES
HAS BEEN REMOVED
6 TO 20 ARE ASSIGNED
[.] KEY IS USED TO
TOP OF PAGE
ADVANCE THE CURSOR
NO ALARMS ACTIVE
THIS FEATURE NOT
PROGRAMMED
THAT DIGITAL INPUT
IS ALREADY IN USE
key while the setpoint is being displayed.