▶ If you want to operate the CytroPac without the STO function, the following
contacts of the mating connector must be bridged as shown in Fig. 19.
+EXT
Fig� 19: Bridged contacts when STO function is disabled
Alternatively, a contact bridge for deactivating the STO function is available as
an accessory for operating the CytroPac without STO functionality.
For a complete list of accessories, see data sheet 51055, see chapter 1.2
"Required and amending documentation".
7�6�3 "Basic" configuration
In the "Basic" configuration, the filling level and temperature sensor, see Fig. 15,
item 1, as well as the filter contamination sensors, see Fig. 15, item 2 and 3 must
be wired and evaluated with the higher-level machine control.
Make sure that the switch-off signals of the oil temperature, filling level and
filter contamination initiate deactivation of the hydraulic power unit in the
"Basic" configuration, for example, by means of deactivation of the 24 VDC
release or the electric power supply.
Bosch Rexroth offers a suitable cable set to connect the sensors with just one
supply line.
For a complete list of accessories, see data sheet 51055, see chapter 1.2
"Required and amending documentation".
1
2
3
4
5
RE 51055-B, Edition 07.2022, Bosch Rexroth AG
Assembly | CytroPac