Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
version 2.7.x before they can be programmed to a two-zone
dependence group.
NOTE!
Only conventional zones (i.e. zone lines with conventional detectors)
should be used in the two-zone dependence function.
For analog / addressable detectors the two-address (unit) dependence
function should be used.
Default for all zones is Group 0 (= no two zone dependence).
Click the current group number (0) for the zone to be programmed.
The zone number displays in the Zone box (down to the right in the
dialog box).
Type the new group number in the Group box.
Click "Apply" to accept and update the Group
The group number for the zone is now changed which is displayed in
the Group Zone list box.
NOTE!
When all changes have been done, check so that two or more zones
are programmed in each group. (A single zone in a group will never
be able to activate any fire alarm!)
141