Expansion Board No. (Address) Setting; Zones Expansion Board 4580 - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
6.1
Board no.
(address)
0
1
2
3
4
5
6.2
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
NOTE! NOTE! NOTE! NOTE! NOTE!
In Win512 version 2.7.x the following is valid for an EBL512 G3
control unit:
4580 boards have to be programmed as 1580 boards.
4581 boards have to be programmed as 1581 boards.
1582 boards cannot be used.
4583 / 1583 boards cannot be used.
1584 boards cannot be used.
1587 board has to be used (selected) when Display Units (1728, 1735,
1736, 1826 and 1828) shall be connected to an EBL512 G3 control
unit United version 2.7.x. No physical board is required – the
Display Units are connected directly in the EBL512 G3 control
unit (RS485).

Expansion board no. (address) setting

The expansion board no. (address) is set via jumpers on the expansion
board respectively.
4580 and 4581
JP2
JP3
Open
Open
Shunted
Open
Open
Shunted
Shunted
Shunted
Open
Open
Shunted
Open
Figure 5.
Expansion boards 4580 - 4582.
expansion board no. (address) setting.

8 zones expansion board 4580

Each board has to be programmed via Win512 version 2.7.x as a
1580 board (4580 cannot be selected), regarding:
Address / Board no. (jumpers "JP2-JP4", see Figure 5 above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
has to be connected an end-of-line capacitor (470 nF).
Connections to "J1:1-16" and "J2" according to drawing 512 G3 - 33.
JP4
JP1
Open
Open
Open
Shunted
Open
Open
Open
Shunted
Shunted
Open
Shunted
Shunted
28
4582
JP2
JP3
Open
Open
Open
Open
Shunted
Open
Shunted
Open
Open
Shunted
Open
Shunted
Jumpers for