5.3

Meaning of the Parameters in the Data Storage Area

1070 072 196-101 (00.06) GB
For each job, a parameter field of 16 words must be reserved in the data field
(DF), the data buffer (DB), or the data module (DM).
The address and the offset of this data storage area is determined with the
parameters P0 to P2 of the R5REQ.
Each parameter field will be assigned a bit in the ABL job bit bar and a bit in
the EBL result bit bar, starting at bit 0.
Below, you find an example of the corresponding data storage area if the pa-
rameter P2 (offset) has the value 0:
Job Bit of the ABL
Corresponding Data
Storage Area
0
DW0 to DW15
1
DW16 to DW31
2
DW32 to DW47
3
DW48 to DW63
4
DW64 to DW79
5
DW80 to DW95
6
DW96 to DW111
7
DW112 to DW127
8
DW128 to DW143
9
DW144 to DW159
10
DW160 to DW175
11
DW176 to DW191
12
DW192 to DW207
13
DW208 to DW223
14
DW224 to DW239
15
DW240 to DW255
The maximally 16 job parameters are distinguished in two groups:
D Protocol-independent parameters
Their contents are always the same, no matter which protocol or which
service is addressed with the subsequent parameters.
D Protocol-dependent parameters
These parameters are different in all protocols or services.
R5REQ
5- -5
Byte Addresses
0 to 31
32 to 63
64 to 95
96 to 127
128 to 159
160 to 191
192 to 223
224 to 255
256 to 287
288 to 319
320 to 351
352 to 383
384 to 415
416 to 447
448 to 479
480 to 511