Perform Monthly Test (H1) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
23
Action
"Access"
"A"
"A"
Write zone numbers
(e.g. 001, 002, 003,
004)
"A"
Rev: 1

Perform monthly test (H1)

The control unit and the installation shall be tested on a regular basis.
If one twelfth of the alarm points are tested each month, the whole
installation will be tested after one year.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S7.)
If a real fire alarm is activated, for example by an alarm point not in
test mode, the normal fire alarm functions will be activated, i.e. fire
alarm presentation, outputs (sounders) activated, routing equipment
(fire brigade tx) activated, etc.
See also chapter "Alphanumeric display in the control unit", page 20.
NOTE! If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in Win512).
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
See also chapter "Perform ZONE TEST (test mode) (H7)", page 117.
Text in display
Perform monthly test
Check that all LEDs light up!
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
Zone to be set in TEST MODE:
??? ??? ??? ???
Zone to be set in TEST MODE:
001 002 003 004
Zones are set in test mode
wait....
Zone in TEST MODE:
001 002 003 004
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H1
ACCEPT
Start test:
ACCEPT
Start test:
ACCEPT
End test:
ACCEPT
73
Comments
According to chapter
"Access", see page 72.
The buzzer (in the C.U.)
sounds and all dots in the
display are shown for 3
seconds. When printer is
available, it will print out:
ABCDE............Z
abcde............z
NOTE! In DBI (Danish)
convention, only one zone.
Press "A" to start the test
mode.
LED "Test mode" (L9)
will light up.
Perform the tests.