Parameters Of Resource Block; Resource Block Parameters - GE FVP110 Maintenance Manual

Table of Contents

Advertisement

GE Energy

Parameters of Resource Block

Relative
Index
Parameter
Index
0
1000
Block Header
1
1001
ST_REV
2
1002
TAG_DESC
3
1003
STRATEGY
4
1004
ALERT_KEY
5
1005
MODE_BLK
6
1006
BLOCK_ERR
7
1007
RS_STATE
8
1008
TEST_RW
9
1009
DD_
RESOURCE
10
1010
MANUFAC_
ID
11
1011
DEV_TYPE
12
1012
DEV_REV
Table 60 Resource Block Parameters
Default
Name
(factory
setting)
0
Null
1
1
O/S
Null
Null
0x00594543
FVP 110 Fieldbus Valve Positioner Manual
Write
Block Tag
Information about this block, including the
=O/S
block tag, DD revision, execution time
Incremented when a change is made to the
parameter settings for the resource block to
indicate the revision level of the settings, and
used to see whether or not there is a change in
parameter settings.
Universal parameter storing the description of
the tag
Universal parameter used by an upper-level
system to classify the function blocks
Universal parameter used as a key to identify
the point from which an alert is issued;
normally used by an upper-level system to
select alerts to provide to a particular operator
who covers a specific area of the plant.
Auto
Universal parameter that indicates the block
operation conditions and is composed of actual
mode, target mode, permitted modes, and
normal mode.
Universal parameter indicating the hardware
and software error statuses related to the block
itself
Indicates the statuses of resource in the
FVP110.
Parameter used to test read and write access
to the FVP110
Name of the device description (DD) containing
the information of this resource block
Manufacturer ID; 5850435 (= 0x594543) is
assigned to Yokogawa Electric Corporation.
ID number of device; 1 or 7 (/EE) is assigned to
the FVP110.
Revision number of the FVP110