GE Energy
Parameters of Resource Block
Relative
Index
Parameter
Index
0
1000
Block Header
1
1001
ST_REV
2
1002
TAG_DESC
3
1003
STRATEGY
4
1004
ALERT_KEY
5
1005
MODE_BLK
6
1006
BLOCK_ERR
7
1007
RS_STATE
8
1008
TEST_RW
9
1009
DD_
RESOURCE
10
1010
MANUFAC_
ID
11
1011
DEV_TYPE
12
1012
DEV_REV
Table 60 Resource Block Parameters
Default
Name
(factory
setting)
0
Null
1
1
O/S
—
—
Null
Null
0x00594543
—
—
FVP 110 Fieldbus Valve Positioner Manual
Write
Block Tag
Information about this block, including the
=O/S
block tag, DD revision, execution time
—
Incremented when a change is made to the
parameter settings for the resource block to
indicate the revision level of the settings, and
used to see whether or not there is a change in
parameter settings.
Universal parameter storing the description of
the tag
Universal parameter used by an upper-level
system to classify the function blocks
Universal parameter used as a key to identify
the point from which an alert is issued;
normally used by an upper-level system to
select alerts to provide to a particular operator
who covers a specific area of the plant.
Auto
Universal parameter that indicates the block
operation conditions and is composed of actual
mode, target mode, permitted modes, and
normal mode.
—
Universal parameter indicating the hardware
and software error statuses related to the block
itself
—
Indicates the statuses of resource in the
FVP110.
Parameter used to test read and write access
to the FVP110
—
Name of the device description (DD) containing
the information of this resource block
—
Manufacturer ID; 5850435 (= 0x594543) is
assigned to Yokogawa Electric Corporation.
—
ID number of device; 1 or 7 (/EE) is assigned to
the FVP110.
—
Revision number of the FVP110
184
Description