Trend Object; View Object; Execution Schedule Of The Fvp110 Function Blocks - GE FVP110 Maintenance Manual

Table of Contents

Advertisement

Trend Object

Trend Object
You can set the parameter so that the function block automatically transmits Trend.
FVP110 has seven non-factory set Trend objects, five for analog data, and two for
discrete data. A single Trend object specifies the trend of one parameter.
Each Trend object has the parameters listed in Table 16. The first four are settable.
Table 16 Execution Schedule of the FVP110 Function Blocks
Sub-index
1
2
3
4
5
6 to 21
21 to 37

View Object

This is the object to form groups of parameters in a block. One of advantages brought
by forming groups of parameters is the reduction of load for data transaction. FVP110
has 12 View objects for Transducer block and four View objects for each Resource, AO
and DI1 and DI2 function block, and each View object has the parameters listed in
Table 17 to Table 22.
Parameters
Block Index
Parameter Relative Index
Sample Type
Sample Interval
Last Update
List of Status
List of Samples
Sets the leading index of the function block that
takes a trend.
Sets the index of parameters taking a trend by
a value relative to the beginning of the function
block.
Specifies how trends are taken. Choose one:
1: Sampled on function block execution.
2: The average value is sampled.
Specifies sampling intervals in units of 1/32 ms.
Sets the integer multiple of the function block
execution cycle.
The last sampling time.
Status part of a sampled parameter.
Data part of a sampled parameter.
97
Configuration
Description