Iti (Message Type I) - Bosch Conettix D6600 Manual

Computer interface of receiver/gateway
Table of Contents

Advertisement

Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols

3.1.14 ITI (Message Type I)

ITI Example
D6500 Byte Description
1
2
h
I
Table 16: ITI (Message Type I) Byte Description
#
Title
1
Header Character
(h)
2
Message Type
3-4
Receiver Number
5
Line/Group
Number
6-8
Spaces
9
Account Number
10
Panel Type
11-14
Account Number
15
G
16
I
17-18
ZZ
19
E
20
W
21
N
22
Trailer Character
20
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
3
4
5
6
7
8
r
r
l
s
s
s
Description
Optional. Check with the computer automation software for
compatibility.
I (Capital i).
Receiver gateway number from 01 to 99.
Line number in the receiver gateway that sent the message.
Three spaces.
First digit account number.
Control panel Type.
Next four digit account number.
Group number.
Open/close (O/C) User ID.
Zone number.
Condition code.
Protection level was.
Protection level is.
Typically, this is HEX 14.
9
10 11 12 13 14 15 16 17 18 19 20 21 22
a
T
a
a
a
a
G
I
Z
Z
E
W
N
t

Advertisement

Table of Contents
loading

This manual is also suitable for:

Conettix d6100ipv6Conettix d6100i

Table of Contents