LG MULTI V HYDRO KIT ARNH963K2A4 Installation Manual page 88

Medium temperature
Table of Contents

Advertisement

PRE-COMMISSIONING
Functions
Table 34: Hydro Kit User Functions, continued.
Function
Outdoor Temp. for Auto Mode
Indoor Air Temp. for Auto
Mode
LWT for Auto Mode
Tank Setting 2
DHW Time Setting
Pump Frequency Setting
(g/min. [l/min.])
Heating Air
Heating Water
Cooling Air
Cooling Water
Heating Temp. Setting
Cooling Temp. Setting
Pump Setting in Heating
Pump Setting in Cooling
Forced Operation
* Deadband is the difference between the upper and lower limit setpoints.
88
Range
• Upper Limit: 50°F~68°F (10°C~20°C)
(Default: 59°F [15°C])
• Lower Limit: -4°F~+41°F (-20°C~+5°C)
(Default: 14°F [-10°C])
• Upper Limit: 68°F~86°F (20°C~30°C)
(Default: 70°F [21°C])
• Lower Limit: 61°F~66.2°F (16°C~19°C)
(Default: 61°F [16°C])
• Upper Limit: 95°F~122°F (35°C~50°C) (De-
fault: 122°F [50°C])
• Lower Limit: 68°F~93.2°F (20°C~34°C)
(Default: 68°F [20°C])
• 00: Perform hot water
• 01: Perform floor heating
• Operation Holding Time: 5 min.~95 min.
(Default: 30 min.)
• Stop Holding Time: 0 min.~600 min. (De-
fault: 180 min.)
5.3 g/min.~24.3 g/min. (20 l/min.~92 l/min.)
(Default: 12.2 g/min. [46 l/min.])
Type: 0, 1, 2, 3 (Default: 0)
Type: 0, 1, 2, 3 (Default: 0)
Type: 0, 1, 2, 3 (Default: 0)
Type: 0, 1, 2, 3 (Default 0)
Type: 0, 1, 2, 3 (Default: 0)
• 00: Outlet / Leaving (Default)
• 01: Inlet / Entering
• 00: Outlet / Leaving (Default)
• 01: Inlet / Entering
• Type: Time, Always (Default: Always)
• OFF Time: 1 min.~60 min. (Default: 1 min.)
• ON Time: 1 min.~60 min. (Default: 2 min.)
• Type: Time, Always (Default : Always)
• OFF Time: 1 min.~60 min. (Default: 1 min.)
• ON Time: 1 min.~60 min. (Default: 2 min.)
20 hr.)
(Default: 10 min.)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Description
Sets the outdoor minimum / maximum temperature for auto mode.
Sets the indoor minimum / maximum temperature for auto mode.
Sets the heating flow minimum / maximum temperature for auto
Sets heating demand priority.
Sets the hot water maintenance / suppression time.
Sets the water flow rate in the water piping.
The temperature of the heating air can be adjusted according to
the field environment preparing for heating claims.
The temperature of the heating water can be adjusted according
to the field environment preparing for heating claims.
The temperature of the cooling air can be adjusted according to
the field environment preparing for cooling claims.
The temperature of the cooling water can be adjusted according to
the field environment preparing for cooling claims.
Set the step value to adjust the hot water temperature thermal
on / off according to the field environment.
Sets the water pipe temperature control standard for heating
in accordance with the field environment.
Sets the water pipe temperature control standard for cooling
in accordance with the field environment.
Sets water pump operation / delay time option for heating.
Sets water pump operation / delay time option for cooling.
Deactivates the logic that drives the water pump itself.
mode.