LG MULTI V HYDRO KIT ARNH963K2A4 Installation Manual page 63

Medium temperature
Table of Contents

Advertisement

Connecting the Dry Contact
(LG Manufactured; Model Nos. PDRYCB100 and PDRYCB300; Optional; Sold Separately)
The Dry Contact unit is designed to enable or disable normal Hydro Kit operations, or determine occupancy for setback temperature setting
through a binary input. A binary output indicates if a system malfunction occurred. A field-supplied binary signal could be triggered using a
timer, keycard switch, door switch, motion detector, or an occupancy sensor.
To install a Dry Contact, see the Dry Contact submittals and / or installation manuals on www.lghvac.com, or contact your LG representative.
• Connect the Dry Contact to Terminal CN-CC on the Hydro Kit PCB.
• See the Pre-Commissioning section for function codes and instructions on accessing Installer mode that will be needed to set up Hydro Kit
accessories.
Figure 57: PDRYCB100 Connect to CN_DRY (Apply Power Source
Through PCB).
DRY CONTACT
PCB
CN-CC
RYL1
RLY2
N
2 1
2
1
Figure 59: PDRYCB300 Installation for Input Contact Closure Only (No
Power Input).
Operation Display
4 4
Error Check Display
3 3
2 2
Dry contact
1 1
Controller
CN_DRY
L
INPUT
Field-Supplied
24V ~
Thermostat
(Field Supplied)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Connecting Optional LG Hydro Kit Accessories
Figure 58: PDRYCB100 Connect to CN_DRY (Apply Power Source
Directly to External Source).
DRY CONTACT
DRY CONTACT
PCB
PCB
CN-CC
RLY2
Figure 60: PDRYCB300 Installation for Input Contact Voltage: DC 12 V,
24 V~.
Connect separate
External voltage of
DC 12 V, AC 24 V
WIRING
Operation Display
4
4
3
3
Error Check Display
2
2
RLY1
1 1
Dry contact
CN_DRY
Controller
L
N
2
1
2
1
24V ~
Field-Supplied
Thermostat
(Field Supplied)
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents